2017-06-23 09:47:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN SHEETS DO NOT INDICATE ANY
 REVISION CLOUDS OR CALL-OUTS AS TO AS-BUILT EQUIPMENT
 OR DEVICES FOR NEW LOCATIONS.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE REVISION CLOUDS OR OTHER DIRECT
 INDICATORS OF AS-BUILT LOCATIONS THAT ARE
 DIFFERENT/CHANGED FROM THE MASTER.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  