| 2017-07-11 11:05:06 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. RISER DIAGRAM SHOWS 3/0 AL CONDUCTORS IN SERVICE |
| | RISER. 3/0 AL IS NOT RATED FOR 200 AMPS. PROVIDE |
| | CORRECTION. NEC 310.15; FBC RE3603.1 |
| | 2. NOTE 1 STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 3. NOTE 13 ALSO REFERENCES THE WRONG CODE SECTION FOR |
| | LIGHTING IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC |
| | 410.16; FBC RE4003.12 |
| | 4. REMOVE ANY NOTES NOT APPLICABLE TO THIS PROJECT. IF |
| | THERE WILL BE A POOL, PROVIDE NOTE THAT STATES THE POOL |
| | WILL BE UNDER SEPARATE PERMIT. FBC 107.2.1 |
| | 5. CIRCUITS 25, 27, 22, 24, AND 26 SHOULD BE AFCI |
| | PROTECTED CIRCUITS BASED ON THE DESCRIPTION. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE3902.12 |
| | 6. PROVIDE COMPLIANCE WITH LIGHTING ENERGY |
| | CONSERVATION: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC |
| | R404.1 |
| | 7. LIGHTING IN BATHTUB OR SHOWER AREAS AND PORCH AREA |
| | SHALL BE SUITABLE FOR DAMP LOCATIONS. THESE AREAS |
| | CURRENTLY SHOW A STANDARD RECESS LIGHT. PROVIDE |
| | CORRECTION. NEC 410.10(A), FBC RE4003.11 |
| | 8. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. THE MASTER CLOSET SHOWS A |
| | STANDARD RECESS LIGHT. PROVIDE CORRECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| | REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET. NEC 210.52; FBC RE3901.2.1 |
| | 10. PROVIDE OUTLET ON REAR OF HOUSE. FOR A ONE FAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS |
| | AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY |
| | ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (6.5 FT) |
| | ABOVE GRADE LEVEL SHALL BE INSTALLED AT THE FRONT AND |
| | BACK OF THE DWELLING. NEC 210.52(E)(1) FBC RE3901.7 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |