Plan Review Notes
Plan Review Notes For Permit 17060886
Permit Number 17060886
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-03 07:24:48FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 215.5 DIAGRAMS OF FEEDERS
 A DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED
 PRIOR TO THE INSTALLATION OF THE FEEDERS.
 SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF
 THE BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE
 APPLYING DEMAND FACTORS, THE DEMAND FACTORS USED, THE
 CALCULATED LOAD
 AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED
  