Plan Review Notes
Plan Review Notes For Permit 17060876
Permit Number 17060876
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-22 06:39:221) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THIS
 SECOND BATHROOM.WPB AMEND. TO FBC SEC. 107.2.1.
 2) IF THIS IS A NEW BATHROOM BEING ADDED INTO AN
 EXISTING STRUCTURE SUBMIT TWO COMPLETE SETS OF PLANS
 THAT SHOWS ALL REQUIRED ELECTRICAL, NEW WALLS, DOORS,
 VENTILATION, WINDOWS, ETC. THE SUBMITTED DOCUMENT
 STATES "2ND BATHROOM " WHICH EXPLAINS NOTHING. IF THIS
 IS A NEW BATHROOM, PERMITS WILL NOT BE ISSUED IN A
 PIECEMEAL FASHION. THE COMPLETE SET OF PLANS SHALL BE
 REVIEWED BY ALL REQUIRED PLAN REVIEW DISCIPLINES. WPB
 AMEND. TO FBC SEC. 107.1, 107.2.1.
 3) SHOW ALL DIMENSIONS OF THE NEW TOILET ROOM ON THE
 COMPLETE SET OF PLANS AND ALSO SHOW THE LENGTH & WIDTH
 DIMENSIONS OF THE SHOWER AND ALL FIXTURE CLEANCES FOR
 THE PLUMBING FIXTURES. 2014 FBC-RES. SEC.P2705.1,P2708.
 4) IF THERE IS AN EXISTING CONCRETE SLAB THAT IS GOING
 TO BE CUT FOR THE INSTALLATION OF NEW PLUMBING SUBMIT A
 SLAB REPAIR DETAIL FOR THE REPAIR OF THE SLAB. SHOW
 SIZE ORF REINFORCING DOWELS, LENGTH, SPACING, EMBEDMENT
 DEPTH, ETC.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW