2017-06-23 13:37:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THERE IS NOLLIFE SAFETY PLAN SUBMITTED WITH THIS
 PLAN SET.
  
 COMPLETE LIFE SAFETY PLANS FOR THIS OCCUPANCY SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 IF THE HOTEL IS TO REMAIN OPEN, PLEASE INCLUDE AND
 INDICATE, WITH DETAILS, HOW THE EXITS WILL BE
 MAINTAINED UNOBSTRUCTED DURING ALL PHASES OF
 CONSTRUCTION.
  
  
  
 2) SHEET A 2 - THE OPENING TO THE HALL WAS CREATED BY
 THE REMOVAL OF A DOOR. THERE IS NO WIDTH OR HEIGHT
 DIMENSION THAT SHOWS COMPLAINCE WITH NFPA 101, CHAPTER
 7, MEANS OF EGRESS.
  
 7.1.5* HEADROOM.
 7.1.5.1 MEANS OF EGRESS SHALL BE DESIGNED AND
 MAINTAINED TO PROVIDE HEADROOM IN ACCORDANCE WITH OTHER
 SECTIONS OF THIS CODE, AND SUCH HEADROOM SHALL BE NOT
 LESS THAN 7 FT 6 IN. (2285 MM), WITH PROJECTIONS FROM
 THE CEILING NOT LESS THAN 6 FT 8 IN. (2030 MM) WITH A
 TOLERANCE OF ?? IN. (?19 MM), ABOVE THE FINISHED FLOOR,
 UNLESS OTHERWISE SPECIFIED BY ANY OF THE FOLLOWING:
 (1) IN EXISTING BUILDINGS, THE CEILING HEIGHT SHALL BE
 NOT LESS THAN 7 FT (2135 MM) FROM THE FLOOR, WITH
 PROJECTIONS FROM THE CEILING NOT LESS THAN 6 FT 8 IN.
 (2030 MM) NOMINAL ABOVE THE FLOOR.
 (2) HEADROOM IN INDUSTRIAL EQUIPMENT ACCESS AREAS AS
 PROVIDED IN 40.2.5.2 SHALL BE PERMITTED.
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3,
 SHALL BE AS FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY
 A MINIMUM WIDTH
  
 7.3.4.1.2 IN EXISTING BUILDINGS, THE WIDTH OF EXIT
 ACCESS SHALL BE PERMITTED TO BE NOT LESS THAN 28 IN.
 (710 MM).
  
 PLEASE PROVIDE/CORRECT INDICATIONS OF COMPLIANCE.
  
  
  
 3) SHEET A 9 - THERE IS A SEATING PLAN INDICATED. THERE
 IS NO OCCUPANY LOAD CALCULATION OR ANY INDICATED
 DIMENSIONS THAT SUPPORT THIS SEATING PLAN AND THE
 OCCUPANCY THAT GOES WITH IT.
  
 PLEASE PROVIDE A DETAILED OCCUPANCY LOAD CALCULATION TO
 SUPPORT THIS SEATING PLAN. THIS CAN BE ADDRESSED ALONG
 WITH # 1 ABOVE.
  
  
  
 4) THERE IS NO INDICATION OF ANY EXISTING FIRE
 SPRINKLER SYSTEM.
  
 PLEASE PROVIDE A NOTE OF COMPLIANCE. ADDITIONALLY, ALL
 WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE BY
 CERTIFIED CONTRACTORS UNDER SEPARATE SHOP DRAWING.
  
  
  
  
 5) THERE IS NO INDICATION OF ANY EXISTING FIRE ALARM
 SYSTEM.
  
 PLEASE PROVIDE A NOTE OF COMPLIANCE. ADDITIONALLY, ALL
 WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE BY
 CERTIFIED CONTRACTORS UNDER SEPARATE SHOP DRAWING.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC