| Date |
Text |
| 2017-06-23 13:37:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | |
| | 1) THERE IS NOLLIFE SAFETY PLAN SUBMITTED WITH THIS |
| | PLAN SET. |
| | |
| | COMPLETE LIFE SAFETY PLANS FOR THIS OCCUPANCY SHALL BE |
| | PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | IF THE HOTEL IS TO REMAIN OPEN, PLEASE INCLUDE AND |
| | INDICATE, WITH DETAILS, HOW THE EXITS WILL BE |
| | MAINTAINED UNOBSTRUCTED DURING ALL PHASES OF |
| | CONSTRUCTION. |
| | |
| | |
| | |
| | 2) SHEET A 2 - THE OPENING TO THE HALL WAS CREATED BY |
| | THE REMOVAL OF A DOOR. THERE IS NO WIDTH OR HEIGHT |
| | DIMENSION THAT SHOWS COMPLAINCE WITH NFPA 101, CHAPTER |
| | 7, MEANS OF EGRESS. |
| | |
| | 7.1.5* HEADROOM. |
| | 7.1.5.1 MEANS OF EGRESS SHALL BE DESIGNED AND |
| | MAINTAINED TO PROVIDE HEADROOM IN ACCORDANCE WITH OTHER |
| | SECTIONS OF THIS CODE, AND SUCH HEADROOM SHALL BE NOT |
| | LESS THAN 7 FT 6 IN. (2285 MM), WITH PROJECTIONS FROM |
| | THE CEILING NOT LESS THAN 6 FT 8 IN. (2030 MM) WITH A |
| | TOLERANCE OF ?? IN. (?19 MM), ABOVE THE FINISHED FLOOR, |
| | UNLESS OTHERWISE SPECIFIED BY ANY OF THE FOLLOWING: |
| | (1) IN EXISTING BUILDINGS, THE CEILING HEIGHT SHALL BE |
| | NOT LESS THAN 7 FT (2135 MM) FROM THE FLOOR, WITH |
| | PROJECTIONS FROM THE CEILING NOT LESS THAN 6 FT 8 IN. |
| | (2030 MM) NOMINAL ABOVE THE FLOOR. |
| | (2) HEADROOM IN INDUSTRIAL EQUIPMENT ACCESS AREAS AS |
| | PROVIDED IN 40.2.5.2 SHALL BE PERMITTED. |
| | |
| | 7.3.4 MINIMUM WIDTH. |
| | 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS |
| | OTHERWISE PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, |
| | SHALL BE AS FOLLOWS: |
| | (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS |
| | COMPONENT IN THIS CHAPTER OR CHAPTERS 11 THROUGH 43 |
| | (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF |
| | THIS CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY |
| | A MINIMUM WIDTH |
| | |
| | 7.3.4.1.2 IN EXISTING BUILDINGS, THE WIDTH OF EXIT |
| | ACCESS SHALL BE PERMITTED TO BE NOT LESS THAN 28 IN. |
| | (710 MM). |
| | |
| | PLEASE PROVIDE/CORRECT INDICATIONS OF COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET A 9 - THERE IS A SEATING PLAN INDICATED. THERE |
| | IS NO OCCUPANY LOAD CALCULATION OR ANY INDICATED |
| | DIMENSIONS THAT SUPPORT THIS SEATING PLAN AND THE |
| | OCCUPANCY THAT GOES WITH IT. |
| | |
| | PLEASE PROVIDE A DETAILED OCCUPANCY LOAD CALCULATION TO |
| | SUPPORT THIS SEATING PLAN. THIS CAN BE ADDRESSED ALONG |
| | WITH # 1 ABOVE. |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF ANY EXISTING FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLIANCE. ADDITIONALLY, ALL |
| | WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE BY |
| | CERTIFIED CONTRACTORS UNDER SEPARATE SHOP DRAWING. |
| | |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATION OF ANY EXISTING FIRE ALARM |
| | SYSTEM. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLIANCE. ADDITIONALLY, ALL |
| | WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE BY |
| | CERTIFIED CONTRACTORS UNDER SEPARATE SHOP DRAWING. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |