| 2017-08-17 10:40:39 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT CONTRACTOR AGREES TO SUBMIT REQUIRED |
| | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| | INSPECTION TO AVOID CONFLICTS/DELAYS. REVISION FEES |
| | WILL APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO |
| | OPTION IS PREFERRED AT THIS TIME. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL |
| | ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM |
| | #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | RESPONSE. REPEAT COMMENT. FRONT PAGE SAYS NO WORST |
| | CASE. NEVERTHELESS, SECOND PAGE SAYS ROTATED 315 |
| | DEGREES AND ORIENTATION SHOWN ON FOLLOWING PAGES IS NOT |
| | THE ACTUAL ORIENTATION OF THE BUILDING. REVISE AS |
| | REQUIRED. PROVIDE CALCULATIONS FOR THE ACTUAL |
| | ORIENTATION OF THE BUILDING. |
| | |
| | B) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT |
| | WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD |
| | FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | RESPONSE: PLANS AND ENERGY CALCULATIONS NEED TO BE |
| | COORDINATED. FLOOR PLAN AND GENERAL WALL LEGEND ON |
| | SHEET 2.1 SPECIFY WOOD FRAMING FOR THE BEARING WALLS L |
| | AND METAL STUDS FOR NON BEARING WALLS. PLANS AND ENERGY |
| | CALCULATIONS NEED TO MATCH. REVISE AS REQUIRED. |
| | |
| | C) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T |
| | MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING |
| | CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | D) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | E) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3 |
| | OF 5. COORDINATE WITH ITEM #1(A) ABOVE. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | F) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5. |
| | WHERE ARE THE 16'-0" X 8'-0" INSULATED DOORS?. SEE |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. NOTE: DOORS WITH |
| | GLAZING NEED TO BE CONSIDERED IN THE WINDOWS AREA AS |
| | REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| | REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE |
| | ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT |
| | FACTOR. |
| | |
| | 2- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED: |
| | CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING |
| | THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF |
| | EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION |
| | #. |
| | RESPONSE: REPEAT COMMENT. CLEARLY IDENTIFY WHICH |
| | ASSEMBLY ON PAGE 5, 6 OR 7 IS GOING TO BE INSTALLED. |
| | NOTE: MAKE SURE ASSEMBLY IS FOR WOOD DECK. IF THE |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES, THEN IT CAN NOT BE USED. |
| | (NOTE: ON 08/22/17 ROOFING CONTRACTOR E-MAILED FRSA |
| | TABLES SHOWING PROPOSED UNDERLAYMENT INSTALLATION). |
| | |
| | 3- TRUSS PACKAGE SUBMITTED: |
| | A) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED |
| | BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. TRUSS ENGINEER TO SEE DESIGN |
| | CRITERIA ON SHEET 2.1 AND REVISE AS REQUIRED. |
| | |
| | B) BASED ON ITEM #3(A) ABOVE REVISED TRUSS PACKAGE TO |
| | BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF |
| | RECORD PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4.2 |
| | CITY AMENDMENTS. |
| | |
| | C) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED |
| | TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER |
| | INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC |
| | 61G15-31.003. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING |
| | HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW |
| | PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |