| 2017-07-11 08:04:49 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. SHOW LOCATION OF ELECTRICAL SERVICE ON PLAN. FBC |
| | 107.2.1 |
| | 2. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. MASTER CLOSETS SHOW |
| | RECESS LIGHTS. PROVIDE CORRECTION. NEC 410.16(B), FBC |
| | RE4003.12 |
| | 3. SMOKE/CO ALARMS ARE REQUIRED TO BE IN THE IMMEDIATE |
| | VICINITY OUTSIDE THE BEDROOMS. THE CURRENT PLACEMENT IN |
| | BOTH HALLWAYS OUTSIDE THE BEDROOMS APPEARS THAT IT IS |
| | TOO FAR FROM THE MASTER BEDROOMS. PROVIDE CORRECTION. |
| | FBC R314.3 |
| | 4. NOTE ON PLAN STATES THAT ALL RECEPTACLES SHALL HAVE |
| | TAMPER RESISTANT PROTECTION PER NEC 406.11. THIS CODE |
| | SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. |
| | PROVIDE CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 5. PROVIDE COMPLIANCE WITH ENERGY CONSERVATION FOR |
| | LIGHTING: "A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS". A NOTE ON PLAN WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |