| 2017-07-18 18:07:53 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEE IS DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- SQUARE FOOTAGE ON THE PROJECT AREA ON SHEET 2.1 IS |
| | MISSING THE AREA FOR THE COVERED PATIO. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- PROJECT DATA ON SHEET 2.1 IS MISSING THE ATTIC LIVE |
| | LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE R301.5 |
| | FBC-5TH EDITION (2014). |
| | |
| | 4- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING |
| | TO THE GREAT ROOM. DOOR NEEDS SELF CLOSING DEVICE AS |
| | REQUIRED BY SEC. R302.5.1 FBC-RESIDENTIAL. |
| | |
| | 5- REVISE DIMENSION "A" ON COMPONENTS AND CLADDING |
| | INFORMATION ON SHEET 4.1 AND 5.1. ACCORDING TO NOTE ON |
| | FIGURE R301.2(7) OF FBC-RESIDENTIAL THE DIMENSION "A" |
| | IS 4 FEET IN ALL CASES NOT 3 FEET. REVISE AS REQUIRED. |
| | |
| | 6- REVISE GARAGE DOORS DESIGN PRESSURES SHOWN ON SHEET |
| | 4.1 AND 5.1. ACCORDING TO NOTES ON PLANS SUBMITTED THE |
| | DESIGN PRESSURES SHOWN ARE BASED ON TABLE R301.2(4) |
| | FBC-RESIDENTIAL. DESIGN PRESSURES SHOWN DON'T |
| | CORRESPOND TO THE REQUIRED DESIGN PRESSURES WHEN THE |
| | PRESSURES ARE MULTIPLIED BY THE 1.21 COEFFICIENT TO |
| | REPRESENT THE EXPOSURE "C". REVISE AS REQUIRED. |
| | |
| | 7- DRAWINGS 7.1, 8.1 AND 9.1 NEED THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS |
| | REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 8-ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE |
| | BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION # (604700) AS REQUIRED BY SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) ENERGY CALCULATIONS NEED TO BE DONE FOR THE ACTUAL |
| | ORIENTATION OF THE BUILDING NOT WORST CASE. REVISE ITEM |
| | #5 AS REQUIRED BY SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) REVISE WALL TYPE ON ITEM #9(B) FOR THE ADJACENT |
| | WALL. PLANS CALL FOR METAL FRAMING ON ONE SIDE AND WOOD |
| | FRAMING ON THE OTHER SIDE. SEC. 101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | E) HEATING INFORMATION SHOWN ON ITEM #13 DOESN'T T |
| | MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING |
| | CALCULATIONS. REVISE AS REQUIRED TO MATCH. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD AS REQUIRED BY SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | G) REVISE WALLS AND WINDOWS ORIENTATION SHOWN ON PAGE 3 |
| | OF 5. COORDINATE WITH ITEM #8(C) ABOVE. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5. |
| | WHERE ARE THE INSULATED DOORS?. SEE PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. DOORS WITH GLAZING NEED TO BE |
| | CONSIDERED IN THE WINDOWS AREA AS REQUIRED BY SEC. |
| | R405.5.3.3 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON ITEM #7 IS REQUIRED WHEN THE |
| | ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE DEFAULT |
| | FACTOR. |
| | |
| | 9- REVISE LOCATION OF CARBON MONOXIDE ALARMS TO COMPLY |
| | WITH SEC. R315.1 FBC-RESIDENTIAL. |
| | |
| | 10- REVISE LOCATION OF SMOKE ALARMS TO COMPLY WITH SEC. |
| | R314.3 FBC-RESIDENTIAL. |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 12- ROOF TILE UNDERLAYMENT FL11288-R15 SUBMITTED: |
| | CLEARLY MARK SPECIFIC UNDERLAYMENT INSTALLATION SHOWING |
| | THE DESIGN PRESSURES OF PROPOSED INSTALLATION TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: SEE PAGES 5,6 AND 7 OF |
| | EVALUATION REPORT SUBMITTED. MARK SPECIFIC APPLICATION |
| | #. |
| | |
| | 13- TRUSS PACKAGE SUBMITTED: |
| | A) TRUSS LAYOUT DOESN'T MATCH ENGINEER'S OF RECORD ROOF |
| | FRAMING PLAN. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | B) DESIGN LOADS DON'T MATCH DESIGN CRITERIA SPECIFIED |
| | BY THE ENGINEER OF RECORD. REVISE AS REQUIRED TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) COMPLETE TRUSS PACKAGE TO BE REVIEWED AND APPROVED |
| | IN WRITING BY THE ENGINEER OF RECORD PRIOR TO SUBMITTAL |
| | T THIS OFFICE. SEC. 107.3.4.2 CITY AMENDMENTS. |
| | |
| | D) TRUSS LAYOUT AND ALL INDIVIDUAL TRUSS DRAWINGS NEED |
| | TO BE SIGNED AND SEALED AND HAVE THE TRUSS ENGINEER |
| | INFORMATION IN ALL DRAWINGS AS REQUIRED BY FAC |
| | 61G15-31.003. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER CLEARLY SPECIFYING |
| | HOW EACH COMMENT IS ADDRESSED TO EXPEDITE THE REVIEW |
| | PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |