Plan Review Notes
Plan Review Notes For Permit 17060800
Permit Number 17060800
Review Stop G
Sequence Number 1
Notes
Date Text
2017-06-20 05:10:091) SUBMIT TWO COPIES OF A HOUSE / FLOOR PLAN SHOWING
 THE LOCATION OF THE TANKLESS WATER HEATER AND THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE WATER HEATER. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR
 THE TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THE BTU LOAD NOTED ON THE PLANS IS 870,000 BTU'S BUT
 MY CALCULATIONS SHOW A BTU LOAD OF 509,000. CLARIFY.
 4) IS THERE A GAS RANGE ON THIS SYSTEM? IF SO, SHOW THE
 GAS RANGE ON BOTH SETS OF PLANS AND INCLUDE THE BTU
 LOAD IN THE DESIGN OF THE SYSTEM AND IF NEW SUBMIT
 MANUF. SPECS. 2014 FBC-FUEL GAS SECS. 402.1, 402.2.
 5) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING ON THE PLAN FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 6) IF THE TOTAL LOAD ON THE SYSTEM IS 870,000 BTU'S
 THEN THE ONE INCH CSST ON THE 2 POUND SYSTEM IS
 UNDERSIZED PER THE TABLE REFERENCED ON THE PLAN. A ONE
 INCH CSST LINE WITH AN EHD OF 31 AT 110 FT. DISTANCE IS
 748,000 BTU'S PER TABLE 402.4 (18). CLARIFY.
 7) SHOW THE LOCATION OF ALL THE NEW & RE-ROUTED GAS
 LINES ON THE FLOOR PLAN AND WHERE THE SLEEVES
 TERMINATE. COMPLY WITH 2014 FBC-FUEL GAS SECS. 404.14,
 404.14.1, 404.14.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  