| Plan Review Notes For Permit 17060795 |
| Permit Number |
17060795 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-21 15:22:19 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060795 | | | 6/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-1: REFER TO NOTE #3 AND SHOW HOW THE | | | EXISTING AC SYSTEMS WILL BE ALTERED TO PROVIDE | | | SEPARATELY CONTROLLED, SEPARATELY ACCESSED, AND | | | SEPARATELY BALANCED AIR FLOWS SYSTEMS TO EACH OF THE | | | TWO TENANT SPACES. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] |
|