| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****SHELL ONLY***** SEPARATE PERMITS AND SUBPERMITS |
| | WILL BE NEEDED FOR TENANT FITOUT WORK. NO CERTIFICATE |
| | OF OCCUPANCY WILL BE GRANTED FOR THE SHELL-ONLY WORK. |
| | |
| | DESIGN SHALL CONFORM TO THE 5TH EDITION OF THE FLORIDA |
| | FIRE PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF |
| | BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | NO SITE OR CIVIL PLANS SUBMITTED SHOWING FIRE HYDRANTS |
| | FOR FIRE DEPARTMENT ACCESS ROADS/LANES. |
| | |
| | PLANS DO NOT INDICATE ANY PORTABLE FIRE EXTINGUISHERS, |
| | EMERGENCY LIGHTING, ILLUMINATED EXIT SIGNS, TACTILE |
| | SIGNAGE. |
| | |
| | PER NFPA 101 SECTION 8.3.2.4, EACH FIRE BARRIER SHALL |
| | BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING |
| | READING "FIRE BARRIER-PROTECT ALL OPENINGS." CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | FIRE PROTECTION BACKFLOW PREVENTER IS LOCATED CLOSER |
| | THAN 40 FEET FROM THE BUILDING. |
| | PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE |
| | FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE |
| | ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO |
| | THAT THEY CAN BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | PROVIDE A DRAWING NOTE INDICATING: AN APPROVED WRITTEN |
| | EMERGENCY PLAN FOR THE EMERGENCY EGRESS OF OCCUPANTS IS |
| | REQUIRED PRIOR TO OCCUPANCY. ALL EMPLOYEES SHALL BE |
| | INSTRUCTED AND PERIODICALLY DRILLED WITH RESPECT TO |
| | THEIR DUTIES UNDER THE PLAN. EMPLOYEES SHALL BE |
| | PERIODICALLY TRAINED OR INSTRUCTED IN THE USE OF |
| | PORTABLE FIRE EXTINGUISHERS. |
| | |
| | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED DURING PLAN RESUBMISSION. |
| | |