| 2017-07-13 10:07:46 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 2. NOTE 8 ON RISER DIAGRAM STATES THE EQUIPMENT |
| | GROUNDING CONDUCTOR (EGC) IS SIZED AT 1/0 COPPER, WHICH |
| | IS NOT PER CODE FOR A 1200 AMP SYSTEM. PROVIDE |
| | CORRECTION. NEC 250.122 |
| | 3. PROVIDE ACTUAL FAULT CURRENT FROM FPL. AN ESTIMATED |
| | VALUE IS NOT ACCEPTABLE. NEC 110.10 |
| | 4. SHEET EP1.2, PLEASE IDENTIFY WHICH LIGHT FIXTURE |
| | MODEL WILL BE USED. FBC 107.2.1 |
| | 5. INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY |
| | CODE. A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE |
| | INDICATION OF SUBMITTAL OF COMPLETION DOCUMENTS PER FBC |
| | C405.7.4 FBC C405.7.3 |
| | 6. LOAD CALCULATIONS PROVIDED IS INCOMPLETE. PROVIDE |
| | ACCURATE LOAD CALCULATIONS TO JUSTIFY SERVICE SIZE. NEC |
| | 215.2, 215.5, 220; FBC 107.2.1 |
| | 7. WHY IS WIRING SHOWN TO THE RTU'S IN UNIT 9, BUT NOT |
| | IN ANY OTHER UNIT? WHY IS THERE NO WIRING SHOWN TO |
| | EMERGENCY AND EXIT LIGHTS REQUIRED? PROVIDE |
| | CLARIFICATION. FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |