Date Text
2017-06-29 11:04:59FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR
 AND A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH.
 LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED
 BY AN ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE
 TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF AT
 LEAST 10 HOURS
  