Plan Review Notes
Plan Review Notes For Permit 17060760
Permit Number 17060760
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-29 12:01:19FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A
 TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS
  