2017-07-13 13:58:08CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. REVISE PANEL LP-1A SCHEDULE TO REFLECT THE
 ADDITIONAL LOAD, SHOWING TOTAL LOAD FOR EACH PHASE OF
 THE PANEL. FBC 107.2.1; NEC 215.5, 408.30
 2. PANEL LP-1A, CIRCUIT 18 IS LABELED AS "NEW E-1 PUMP
 STATION". IS THIS GPS-1? PLEASE CLARIFY AND/OR CORRECT.
 FBC 107.2.1, 408.4
 3. PROVIDE PANEL LP PANEL SCHEDULE, SHOWING ANY NEW OR
 ALTERED CIRCUITS, AND LOAD ON PANEL. FBC 107.2.1; NEC
 215.5, 408.30
 4. PROVIDE DETAIL OF LOAD TABULATION FOR SWBD-1. IS
 THIS LOAD TABULATION INCLUDE ALL LOADS? PROVIDE
 CLARIFICATION. FBC 107.2.1; NEC 215.5, 220, 408.30
 5. PROVIDE GRINDER PUMP SPEC SHEET. WHAT IS THE CURRENT
 DRAW FOR THIS? WHY DOES THE DETAIL SHOW THAT THE PUMP
 POWER USES A 120 VOLT LINE WIRE WITH THE EQUIPMENT
 GROUNDING CONDUCTOR(EGC)? THE EGC SHOULD NOT HAVE ANY
 CURRENT FLOW ON IT. NEC 110.3, 250.6, 250.26
 6. ONE LINE DIAGRAM SHOW TYPE AC CABLE INSTALLED IN 4"
 CONDUIT TO PUMP RCW-P-5. TYPE AC CABLE IS NOT PERMITTED
 IN WET OR DAMP LOCATIONS OR WHERE EXPOSED TO CORROSIVE
 CONDITIONS. PROVIDE CORRECTION. NEC 320.12
 7. TYPE AC CABLE MENTIONED IN COMMENT #5 SHOWS A #6 EGC
 TO PUMP. EGC IS REQUIRED TO BE SIZED PER NEC 250.122.
 WHAT IS THE OVERCURRENT PROTECTION ON THE MOTOR?
 PROVIDE CORRECTION AND DETAILS OF MOTOR CURRENT
 REQUIREMENTS. NEC 110.3, 250.122, 430.22
 8. PROVIDE DISONNECTS FOR MOTORS WITHIN SIGHT OF MOTOR,
 OR EXPLANATION OF SAFETY PROCEDURES IF THE EXCEPTION TO
 THIS RULE IS INTENDED. NEC 430.102(B)
 9. WIRE SIZE FEEDING RCW-VFD-5 IS DIFFERENT SIZE FROM
 THE WIRE FEEDING PUMP RCW-P-5. THIS DISCREPANCY DOES
 NOT EXIST ON THE OTHER PUMPS. PLEASE CLARIFY AND/OR
 CORRECT. FBC 107.2.1, NEC 310.15(B)(16)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  