| 2017-07-13 13:58:08 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. REVISE PANEL LP-1A SCHEDULE TO REFLECT THE |
| | ADDITIONAL LOAD, SHOWING TOTAL LOAD FOR EACH PHASE OF |
| | THE PANEL. FBC 107.2.1; NEC 215.5, 408.30 |
| | 2. PANEL LP-1A, CIRCUIT 18 IS LABELED AS "NEW E-1 PUMP |
| | STATION". IS THIS GPS-1? PLEASE CLARIFY AND/OR CORRECT. |
| | FBC 107.2.1, 408.4 |
| | 3. PROVIDE PANEL LP PANEL SCHEDULE, SHOWING ANY NEW OR |
| | ALTERED CIRCUITS, AND LOAD ON PANEL. FBC 107.2.1; NEC |
| | 215.5, 408.30 |
| | 4. PROVIDE DETAIL OF LOAD TABULATION FOR SWBD-1. IS |
| | THIS LOAD TABULATION INCLUDE ALL LOADS? PROVIDE |
| | CLARIFICATION. FBC 107.2.1; NEC 215.5, 220, 408.30 |
| | 5. PROVIDE GRINDER PUMP SPEC SHEET. WHAT IS THE CURRENT |
| | DRAW FOR THIS? WHY DOES THE DETAIL SHOW THAT THE PUMP |
| | POWER USES A 120 VOLT LINE WIRE WITH THE EQUIPMENT |
| | GROUNDING CONDUCTOR(EGC)? THE EGC SHOULD NOT HAVE ANY |
| | CURRENT FLOW ON IT. NEC 110.3, 250.6, 250.26 |
| | 6. ONE LINE DIAGRAM SHOW TYPE AC CABLE INSTALLED IN 4" |
| | CONDUIT TO PUMP RCW-P-5. TYPE AC CABLE IS NOT PERMITTED |
| | IN WET OR DAMP LOCATIONS OR WHERE EXPOSED TO CORROSIVE |
| | CONDITIONS. PROVIDE CORRECTION. NEC 320.12 |
| | 7. TYPE AC CABLE MENTIONED IN COMMENT #5 SHOWS A #6 EGC |
| | TO PUMP. EGC IS REQUIRED TO BE SIZED PER NEC 250.122. |
| | WHAT IS THE OVERCURRENT PROTECTION ON THE MOTOR? |
| | PROVIDE CORRECTION AND DETAILS OF MOTOR CURRENT |
| | REQUIREMENTS. NEC 110.3, 250.122, 430.22 |
| | 8. PROVIDE DISONNECTS FOR MOTORS WITHIN SIGHT OF MOTOR, |
| | OR EXPLANATION OF SAFETY PROCEDURES IF THE EXCEPTION TO |
| | THIS RULE IS INTENDED. NEC 430.102(B) |
| | 9. WIRE SIZE FEEDING RCW-VFD-5 IS DIFFERENT SIZE FROM |
| | THE WIRE FEEDING PUMP RCW-P-5. THIS DISCREPANCY DOES |
| | NOT EXIST ON THE OTHER PUMPS. PLEASE CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1, NEC 310.15(B)(16) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |