| 2017-06-19 17:38:44 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SPECIFY THE TYPE OF FLOORING THAT YOU ARE PROPOSING |
| | TO INSTALL. FBC 107.2.1 |
| | |
| | 2) TILE, WOOD AND OTHER TYPES OF HARD FLOORING ARE |
| | REQUIRED TO COMPLY WITH SOUND TRANSMISSION LIMITATIONS. |
| | SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND |
| | INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED |
| | FOR THE APPLICABLE CONSTRUCTION CONDITIONS. |
| | FBC 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) SUBMIT TWO COPIES OF THE FLOORINGS SOUND INSULATION |
| | PRODUCT'S TEST REPORT THAT SHOWS COMPLIANCE WITH FBC |
| | 603 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION |
| | 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL |
| | BE PERMITTED IN BUILDINGS OF TYPE I OR II CONSTRUCTION |
| | IN THE FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH |
| | SECTIONS 603.1.1 THROUGH 603.1.3: |
| | 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| | PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 25. |
| | EXCEPTIONS: |
| | 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26. |
| | |
| | 4) SUBMIT TWO COPIES OF THE FLOORINGS SOUND INSULATION |
| | PRODUCT'S TEST REPORT THAT SHOWS COMPLIANCE WITH FBC |
| | 2603 FOAM PLASTIC INSULATION |
| | 2603.3 SURFACE-BURNING CHARACTERISTICS. UNLESS |
| | OTHERWISE INDICATED IN THIS SECTION, FOAM PLASTIC |
| | INSULATION AND FOAM PLASTIC CORES OF MANUFACTURED |
| | ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE |
| | THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN |
| | 450 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR |
| | USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. LOOSE |
| | FILL-TYPE FOAM PLASTIC INSULATION SHALL BE TESTED AS |
| | BOARD STOCK FOR THE FLAME SPREAD AND SMOKE-DEVELOPED |
| | INDEXES. |
| | |
| | |
| | |