| Plan Review Notes For Permit 17060686 |
| Permit Number |
17060686 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-18 15:33:40 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060686 | | | 7/12/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE 1ST REVIEW COMMENT PRINTED BELOW WAS NOT | | | ADDRESSED. PLEASE PROVIDE SIGNED AND SEALED ENGINEERING | | | FOR THE SITE-BUILT REFRIGERATION ROOFTOP RACK. SEE THE | | | 1ST REVIEW PRINTED BELOW. | | | | | | 2) THE REFRIGERATION UNIT IDENTIFICATIONS (RTU'S 1-4) | | | LISTED ON THE STRUCTURAL ENGINEERING SUBMITTAL FROM | | | CARL FORBES P.E. DO NOT MATCH THE IDENTIFICATIONS | | | LISTED ON THE PLANS WHICH ARE COMP # 1 & 2, AND COND #1 | | | & 2. PLEASE CORRECT THE ID'S ON THE SUBMITTAL TO MATCH. | | | | | | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060686 | | | 7/12/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED "SHOP DRAWING" APPEARS TO HAVE BEEN | | | PRODUCED BY THE ARCHITECT ESENAT-COHEN ARCHITECT, P.A. | | | AND IS ACTUALLY A SITE BUILT ROOF STAND AND NOT A | | | SHOP-BUILT PRODUCT. THE ARCHITECT MUST PROVIDE HIS | | | OFFICIAL SEAL AND SIGNATURE ON THE DRAWING PER SECTION | | | 61G15-16.003 FAC, AND PROVIDE THE WIND LOAD DESIGN | | | CRITERIA AS OUTLINED IN SECTION 1609 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|