| Plan Review Notes For Permit 17060686 |
| Permit Number |
17060686 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-28 09:29:28 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE. | | | | | | 1) THE EQUIPMENT SUPPORT STAND INCLUDED ON THIS PERMIT | | | DIFFER THAN THE LAYOUT OF THE ROOFTOP AC EQUIPMENT | | | SHOWN ON MASTER PERMIT 13090329. PLEASE PROVIDE REVISED | | | SIGHT LINE DRAWINGS VERIFYING THAT THE FINAL ROOFTOP | | | EQUIPMENT LAYOUT, INCLUDING FINAL HEIGHT, ARE STILL | | | SCREENED FROM VIEW IN ACCORDANCE WITH THE BROADWAY | | | MIXED USE DISTRICT REQUIREMENTS. PLEASE NOTE THAT THE | | | REVISED LAYOUT NEEDS TO BE REFLECTED ON THE MASTER | | | PERMIT PLANS AS A REVISION. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] | | 2017-06-15 14:27:08 | ROUTED TO ERIC SCHNEIDER |
|