| 2017-06-27 15:19:02 | FAILED |
| | |
| | PLEASE PROVIDE WRITTEN RESPONSES. |
| | |
| | 1) PROVIDE THE WIDTH OF THE DUMPSTER ENCLOSURE OPENING |
| | ON THE PLAN. IT MUST CONTAIN A MINIMUM 12 FOOT 6 INCH |
| | WIDE OPENING (NO DIMENSION PROVIDED). |
| | |
| | 2) THE OVERALL DUMPSTER ENCLOSURE DEPTH DOES NOT MEET |
| | CITY STANDARDS. PROVIDE A LETTER FROM THE CITY?S |
| | SANITATION DEPARTMENT THAT THE 10 FOOT DEPTH MEETS IS |
| | APPROVED. |
| | |
| | 3) SECTION 94-221(D)(10) OF THE ZONING AND LAND |
| | DEVELOPMENT REGULATIONS REQUIRES THAT DUMPSTERS FOR |
| | FOOD SERVICE BUSINESSES SHALL BE FULLY ENCLOSED AND |
| | AIR-CONDITIONED. THE CHIEF BUILDING OFFICIAL DETERMINED |
| | THAT AIR-CONDITIONING THE DUMPSTER ENCLOSURE WOULD NOT |
| | COMPLY WITH THE ENERGY CODE REQUIREMENTS, SO THE |
| | DUMPSTER DOES NOT NEED TO BE AIR-CONDITIONED. HOWEVER, |
| | THE FULLY ENCLOSED DUMPSTER NEEDS TO HAVE SOME SORT OF |
| | EXHAUST FAN. PROVIDE THE DETAILS ON HOW THE ENCLOSURE |
| | WILL BE VENTED. PLEASE NOTE THAT THE FAN (MECHANICAL |
| | EQUIPMENT) SHALL BE SCREENED IN ACCORDANCE WITH SECTION |
| | 94-221(D)(8). THE NOTE ON THE PLAN TO REFERENCE THE |
| | MASTER PERMIT DOES NOT APPLY SINCE NOTHING RELATING TO |
| | THE DUMPSTER ENCLOSURE WAS APPROVED AS PART OF THE |
| | MASTER BUILDING PERMIT BY ZONING. ALL DUMPSTER |
| | ENCLOSURE DETAILS AND SPECIFICATIONS ARE TO BE INCLUDED |
| | AND APPROVED BY THIS PERMIT. |
| | |
| | 4) PROVIDE TWO COPIES OF ALL PLANS. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |
| 2017-06-15 14:26:31 | ROUTED TO ERIC SCHNEIDER |