Plan Review Notes
Plan Review Notes For Permit 17060677
Permit Number 17060677
Review Stop B
Sequence Number 3
Notes
Date Text
2017-08-02 11:47:292014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 COMMENT FROM PREVIOUS LISTS:
  
 2) SEMI-COMPLIED. FOR ALL ROOF TOP EQUIPMENT, PLEASE
 PROVIDE THE DETAIL FOR THE ATTACHMENT FROM THE ROOF
 STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3RD REVIEW - PLAN WAS NOT REVISED. RESPONSE LETTER
 PROVIDES A DESCRIPTION OF A DETAIL (APPEARS TO BE
 7-A5.01, ALREADY ON PLAN), AND AT THE END OF THE
 DESCRIPTION STATES "THE UNIT WILL BE CONNECTED TO THE
 NEW SUPPORT STEEL USING 1/2' STAINLESS STEEL BOLTS."
 RESPONSE LETTER ALSO REFERS TO ATTACHED PRODUCT SHEET.
  
 COMMENT #2 REQUESTS "A DETAIL FOR ATTACHMENT FROM THE
 ROOF STAND TO THE EQUIPMENT ABOVE". THE PRODUCT SHEET
 CANNOT BE USED TO SPECIFY ATTACHMENT (NOT SIGNED AND
 SEALED, NO WIND DESIGN CRITERIA, LACKS FASTENING
 SPECIFICATION.
  
 THE RESPONSE LETTER DOES NOT ADDRESS THE COMMENT; 1/2"
 STAINLESS STEEL BOLTS IS TOO GENERAL AND THE RESPONSE
 LETTER IS NOT RETAINED AS A PART OF THE PERMIT
 DOCUMENTS.
  
 EITHER A SEPARATE DETAIL CAN BE PROVIDED, OR THE DETAIL
 ON THE PLAN CAN BE MODIFIED TO INCLUDE THE
 SPECIFICATION.
  
 PLEASE REVISE PLAN TO INCLUDE THE INFORMATION
 REQUESTED; ALSO INCLUDE INFORMATION SUCH AS NUMBER
 REQUIRED, OR FASTENING PATTERN AS APPLICABLE, DIAMETER,
 LENGTH.
  
 THIS MAY BE A PROVISO ITEM UPON REQUEST. PLANS HAVE
 BEEN STAMPED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 SAMANTHA HILL
 (FOR JAMES A. WITMER BN, PX, CBO)
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6724
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  