| 2017-07-19 17:44:54 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060677 | | | 7/19/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE AN AHRI | | | CERTIICATE FOR THE NEW 15 TON SYSTEM- SECTION C101.4.7 | | | FBC-14 ENERGY CONSERVATION. | | | | | | 2) SHEET M1.01: THE O/A INTAKE OPENING FOR THE | | | MECHANCIAL ROOM IS NOT IN COMPLIANCE WITH SECTION 401.4 | | | (2) WHICH SPECIFIES A MINIMUM 10' CLEARANCE DISTANCE | | | FROM THE PARKING LOT AREA. | | | | | | 3) M1.01: THE 9" FLEX DUCT SUPPLYING THE TWO 250 CFM | | | DIFFUSERS OVER THE DISPLAY BOX 2 AREA IS UNDERSIZED AT | | | 1.0 W.G PRESSURE. PLEASE UPSIZE THE DUCT TO MINIMUM 10" | | | DIAMETER. | | | | | | 4) M2.01: PLEASE ADD THE 0.6 CFM/SF CALCULATION TO THE | | | TORAL REQUIRED CFMS OF O/A FOR THE SHOWROOM- TABLE | | | 403.3. | | | | | | 4) A5.01: INDICATE HOW THE CONDENSER WILL BE ANCHORED | | | TO THE NEW SUPPORT STEEL- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|