2017-07-19 17:44:542ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060677
 7/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED PLEASE PROVIDE AN AHRI
 CERTIICATE FOR THE NEW 15 TON SYSTEM- SECTION C101.4.7
 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET M1.01: THE O/A INTAKE OPENING FOR THE
 MECHANCIAL ROOM IS NOT IN COMPLIANCE WITH SECTION 401.4
 (2) WHICH SPECIFIES A MINIMUM 10' CLEARANCE DISTANCE
 FROM THE PARKING LOT AREA.
  
 3) M1.01: THE 9" FLEX DUCT SUPPLYING THE TWO 250 CFM
 DIFFUSERS OVER THE DISPLAY BOX 2 AREA IS UNDERSIZED AT
 1.0 W.G PRESSURE. PLEASE UPSIZE THE DUCT TO MINIMUM 10"
 DIAMETER.
  
 4) M2.01: PLEASE ADD THE 0.6 CFM/SF CALCULATION TO THE
 TORAL REQUIRED CFMS OF O/A FOR THE SHOWROOM- TABLE
 403.3.
  
 4) A5.01: INDICATE HOW THE CONDENSER WILL BE ANCHORED
 TO THE NEW SUPPORT STEEL- SECTION 301.15.
  