| 2017-07-21 15:01:39 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS (2ND REVIEW): |
| | |
| | 1. LIGHTING PLAN SHOWS 1 OFFICE AND 2 BATHROOMS WITH |
| | OCCUPANCY SENSORS, BUT NO OTHER AREAS SHOW THE REQUIRED |
| | CONTROL. THE MECHANICAL ROOM HAS A STANDARD SWITCH, AND |
| | THE SALES AREAS SAY THAT THEY ARE TO BE CONNECTED TO |
| | LCP, BUT NO DETAIL IS PROVIDED FOR LCP AND NO OCCUPANCY |
| | SENSORS ARE SHOWN ON PLAN. CLARIFY AND/OR CORRECT. FBC |
| | 107.2.1, C405.2.2 |
| | 2. SHOW LOCATION OF PANEL MDP ON POWER PLAN. FBC |
| | 107.2.1 |
| | 3. AHU-1 IS BEING FED FROM PANEL AC AND IS SHOWN ON A |
| | 20 AMP BREAKER WITH #12 WIRE. SPECS FROM THE MECHANICAL |
| | PLAN STATE THAT THE MINIMUM CIRCUIT AMPACITY FOR THIS |
| | IS 79 AMPS AND THE MAXIMUM OVER CURRENT PROTECTION |
| | (OCP) IS SHOWN AS 80 AMP. PROVIDE CORRECTION. NEC |
| | 110.3, 310.15(B)(16), 440.22(C), FBC 107.2.1 |
| | 4. LOAD CALCULATION FOR PANEL AC DOES NOT INCLUDE THE |
| | ACCURATE LOAD FOR AHU-1. IT ALSO SHOWS THE MOTOR LOAD |
| | AT 100% INSTEAD OF THE REQUIRED 125%. PROVIDE |
| | CORRECTION AND UPDATE PANEL AC AND PANEL C WITH THIS |
| | INFORMATION. IT APPEARS THAT PANEL AC OCP AND POSSIBLY |
| | PANEL C WILL BE OVERLOADED WHEN THIS IS INCLUDED. MAKE |
| | ANY ADJUSTMENTS TO EQUIPMENT OR OCP AS NEEDED. FBC |
| | 107.2.1, NEC 220, 215.2, 215.3, 408.30 |
| | 5. RISER DIAGRAM NEEDS TO BE COMPLETE WITH ALL WIRE |
| | SIZES TO CONFIRM CODE COMPLIANCE. VERIFYING WIRE AT |
| | LATER DATE IS NOT ACCEPTABLE. PROVIDE CORRECTION. NEC |
| | 215.5, FBC 107.2.1 |
| | 6. RISER DIAGRAM STATES THAT THE ESTIMATED FAULT |
| | CURRENT IS 21,000, WHICH MATCHES THE RATING OF PANEL |
| | MDP. THE CALCULATION PROVIDED STATES THAT THE FAULT |
| | CURRENT IS 23,192, WHICH IS IN EXCESS OF THE RATING OF |
| | PANEL MDP. PROVIDE LETTER FROM POWER COMPANY WITH |
| | ACCURATE FAULT CURRENT, ADJUST EQUIPMENT AS NECESSARY. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL A, |
| | SEVERAL LOADS ARE MISSING/NOT INCLUDED. SIZE EQUIPMENT |
| | AND OCP AS NEEDED. NEC 220, 215.2, 215.3, 408.30 |
| | 8. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE TO |
| | CONFIRM THAT THE SERVICE IS NOT OVERLOADED. WHILE THE |
| | OTHER SPACE IS STATED AS BEING VACANT, IF IT IS USED IN |
| | THE FUTURE THIS COULD BE A PROBLEM. OUT OF THE |
| | AVAILABLE 400 AMP SERVICE, APPROXIMATELY 300 AMPS ARE |
| | REQUIRED FOR THIS TENANT. PROVIDE FULL LOAD |
| | CALCULATION, UPGRADE SERVICE IF NECESSARY. NEC 220, |
| | 230.31, FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |