2017-07-21 15:01:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 1. LIGHTING PLAN SHOWS 1 OFFICE AND 2 BATHROOMS WITH
 OCCUPANCY SENSORS, BUT NO OTHER AREAS SHOW THE REQUIRED
 CONTROL. THE MECHANICAL ROOM HAS A STANDARD SWITCH, AND
 THE SALES AREAS SAY THAT THEY ARE TO BE CONNECTED TO
 LCP, BUT NO DETAIL IS PROVIDED FOR LCP AND NO OCCUPANCY
 SENSORS ARE SHOWN ON PLAN. CLARIFY AND/OR CORRECT. FBC
 107.2.1, C405.2.2
 2. SHOW LOCATION OF PANEL MDP ON POWER PLAN. FBC
 107.2.1
 3. AHU-1 IS BEING FED FROM PANEL AC AND IS SHOWN ON A
 20 AMP BREAKER WITH #12 WIRE. SPECS FROM THE MECHANICAL
 PLAN STATE THAT THE MINIMUM CIRCUIT AMPACITY FOR THIS
 IS 79 AMPS AND THE MAXIMUM OVER CURRENT PROTECTION
 (OCP) IS SHOWN AS 80 AMP. PROVIDE CORRECTION. NEC
 110.3, 310.15(B)(16), 440.22(C), FBC 107.2.1
 4. LOAD CALCULATION FOR PANEL AC DOES NOT INCLUDE THE
 ACCURATE LOAD FOR AHU-1. IT ALSO SHOWS THE MOTOR LOAD
 AT 100% INSTEAD OF THE REQUIRED 125%. PROVIDE
 CORRECTION AND UPDATE PANEL AC AND PANEL C WITH THIS
 INFORMATION. IT APPEARS THAT PANEL AC OCP AND POSSIBLY
 PANEL C WILL BE OVERLOADED WHEN THIS IS INCLUDED. MAKE
 ANY ADJUSTMENTS TO EQUIPMENT OR OCP AS NEEDED. FBC
 107.2.1, NEC 220, 215.2, 215.3, 408.30
 5. RISER DIAGRAM NEEDS TO BE COMPLETE WITH ALL WIRE
 SIZES TO CONFIRM CODE COMPLIANCE. VERIFYING WIRE AT
 LATER DATE IS NOT ACCEPTABLE. PROVIDE CORRECTION. NEC
 215.5, FBC 107.2.1
 6. RISER DIAGRAM STATES THAT THE ESTIMATED FAULT
 CURRENT IS 21,000, WHICH MATCHES THE RATING OF PANEL
 MDP. THE CALCULATION PROVIDED STATES THAT THE FAULT
 CURRENT IS 23,192, WHICH IS IN EXCESS OF THE RATING OF
 PANEL MDP. PROVIDE LETTER FROM POWER COMPANY WITH
 ACCURATE FAULT CURRENT, ADJUST EQUIPMENT AS NECESSARY.
 NEC 110.9, 110.10
 7. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL A,
 SEVERAL LOADS ARE MISSING/NOT INCLUDED. SIZE EQUIPMENT
 AND OCP AS NEEDED. NEC 220, 215.2, 215.3, 408.30
 8. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE TO
 CONFIRM THAT THE SERVICE IS NOT OVERLOADED. WHILE THE
 OTHER SPACE IS STATED AS BEING VACANT, IF IT IS USED IN
 THE FUTURE THIS COULD BE A PROBLEM. OUT OF THE
 AVAILABLE 400 AMP SERVICE, APPROXIMATELY 300 AMPS ARE
 REQUIRED FOR THIS TENANT. PROVIDE FULL LOAD
 CALCULATION, UPGRADE SERVICE IF NECESSARY. NEC 220,
 230.31, FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER