2017-06-21 13:25:201ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY
 CONSERVATION CODES.
 PERMIT #17060677
 6/21/17
  
 1) SUBMIT TWO COPIES OF THE DEVELOPMENT SERVICES
 DEPARTMENT AC CHANGEOUT FORM FOR THE REPLACED 15-TON
 AIR HANDLER AND THE TWO 6-TON CONDENSER UNITS.
  
 2) REFER TO SECTION C101.4.7 EXCEPTIONS FBC-14 ENERGY
 CONSERVATION: MATCHING SYSTEMS ARE REQUIRED FOR
 REPLACEMENT OF THE 15-TON SYSTEM AND THE MATCH MUST BE
 VERIFIED BY ANYONE OF THE FOLLOWING MEANS: A) AHRI
 CERTIFICATE B) ACCREDITTED LABORATORY C) MANUFACTURER'S
 LETTER D) LETTER FROM A FL. REGISTERED PROFESSIONAL
 ENGINEER.
  
 3) MECHANICAL PLAN M3.01: PROVIDE AN AC EQUIPMENT
 SCHEDULE ON THE PLAN.
  
 4) M3.01: INDICATE THE TYPE OF RETURN AIR DOOR TO BE
 INSTALLED AT THE MECHANICAL/ELECTRICAL ROOM. PLEASE
 NOTE THAT THE DOOR SHALL BE NON-COMBUSTIBLE PER SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION, AND SECTION 602
 FBC-14 MECHANICAL. PLEASE REVIEW ALL SUB-SECTIONS OF
 SECTION 602 FOR ALL MATERIALS ALLOWED TO BE IN THE
 PLENUM INCLUDING ELECTRICAL EQUIPMENT AND WIRING, FOAM
 PLASTIC ETC. PLEASE NOTE THAT NO FUEL-FIRED APPLIANCES
 OR EQUIPMENT ARE PERMITTED TO BE LOCATED IN THE ROOM-
 SECTION 602.1.
  
 5) M3.01: REFER TO SECTION 606.2.1 FBC-14 MECHANICAL
 AND SHOW THE LOCATION(S) OF THE REQUIRED SMOKE
 DETECTOR(S) IN THE MECHANICAL ROOM.
  
 6) M3.01: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 7) A3.01 & M3.01: THE TWO NEW OFFICES 102, AND
 EXECUTIVE OFFICE102 ROOMS BEING CREATED WILL REQUIRE
 RETURN AIR TO ACHIEVE BALANCED AIR FOR THE SYSTEM-
 SECTION 601.5. PLEASE PROVIDE DETAILS AND INDICATE THE
 AMOUNT OF SUPPLY CFMS AT EACH DIFFUSER LOCATION IN THE
 NEW ROOMS. IT MAY BE HELPFUL FOR THE DESIGN
 PROFESSIONAL TO ASSIGN DIFFERENT ROOM NUMBERS TO EACH
 OF THE THREE OFFICES.
  
 8) M3.01: PROVIDE EXHAUST VENTILATION FOR THE NEW
 TOILET ROOMS- TAVBLE 403.3.
  
 9) SHOW THE LOCATIONS OF THE NEW 6-TON CONDENSERS AND
 PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15 FBC-14 MECHANICAL.
  