Plan Review Notes
Plan Review Notes For Permit 17060677
Permit Number 17060677
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-19 14:06:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 3.01 - ON THE WAY TO THE FRONT EXIT DOOR,
 THERE IS A SPACE TO GO THROUGH BETWEEN DISPLAY 8 & 6 ON
 THE DIAGONAL. THE DIMENSION OF THIS DIAGONAL SPACE IS
 NOT INDICATED AND SHALL MEET THE MINIMUM REQUIREMENTS
 OF THE CODE.
  
 NFPA 101 CHAPTER 7 MEANS OF EGRESS
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3,
 SHALL BE AS FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY
 A MINIMUM WIDTH
  
  
 NFPA 101 CHAPTER 36, NEW MERCANTILE
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) INCLEAR WIDTH.
  
  
 PLEASE PROVIDE THE APPLICABLE DIMENSION AND ENSURE THAT
 IT MEETS THE MINIMUM REQUIRMENTS AT ALL TIMES.
  
  
  
  
 2) SHEET A 3.01 - THERE IS A NEW DOOR INDICATED LEADING
 TO THE VESTIBULE. THERE IS NO DOOR SCHEDULE FOR THIS
 DOOR INCLUDING, BUT NOT LIMITED TO, EXIT HARDWARE. ALL
 OTHER DOORS ARE ALSO NOT ACCOUNTED FOR ON A DOOR
 SCHEDULE.
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE SPECIAL REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
  
 PLEASE REIVEW AND PROVIDE A DETAILED DOOR SCHEDULE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  