| 2017-06-19 14:06:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 3.01 - ON THE WAY TO THE FRONT EXIT DOOR, |
| | THERE IS A SPACE TO GO THROUGH BETWEEN DISPLAY 8 & 6 ON |
| | THE DIAGONAL. THE DIMENSION OF THIS DIAGONAL SPACE IS |
| | NOT INDICATED AND SHALL MEET THE MINIMUM REQUIREMENTS |
| | OF THE CODE. |
| | |
| | NFPA 101 CHAPTER 7 MEANS OF EGRESS |
| | |
| | 7.3.4 MINIMUM WIDTH. |
| | 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS |
| | OTHERWISE PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, |
| | SHALL BE AS FOLLOWS: |
| | (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS |
| | COMPONENT IN THIS CHAPTER OR CHAPTERS 11 THROUGH 43 |
| | (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF |
| | THIS CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY |
| | A MINIMUM WIDTH |
| | |
| | |
| | NFPA 101 CHAPTER 36, NEW MERCANTILE |
| | |
| | 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN. |
| | (915 MM) INCLEAR WIDTH. |
| | |
| | |
| | PLEASE PROVIDE THE APPLICABLE DIMENSION AND ENSURE THAT |
| | IT MEETS THE MINIMUM REQUIRMENTS AT ALL TIMES. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 3.01 - THERE IS A NEW DOOR INDICATED LEADING |
| | TO THE VESTIBULE. THERE IS NO DOOR SCHEDULE FOR THIS |
| | DOOR INCLUDING, BUT NOT LIMITED TO, EXIT HARDWARE. ALL |
| | OTHER DOORS ARE ALSO NOT ACCOUNTED FOR ON A DOOR |
| | SCHEDULE. |
| | |
| | 36.2.2.2 DOORS. |
| | 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| | TO THE SPECIAL REQUIREMENTS OF 7.2.1. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 |
| | THROUGH 23. |
| | |
| | |
| | PLEASE REIVEW AND PROVIDE A DETAILED DOOR SCHEDULE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |