2017-06-22 18:06:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.1 MANUAL LIGHTING CONTROLS.
 ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS
 THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND
 C405.2.1.2.
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR
 THE LIGHTING SERVING THAT AREA. THE REQUIRED CONTROLS
 SHALL BE LOCATED WITHIN THE AREA SERVED BY THE CONTROLS
 OR BE A REMOTE SWITCH THAT IDENTIFIES THE LIGHTS SERVED
 AND INDICATES THEIR STATUS.
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT
 PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER.
  
 EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE
 PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS,
 STAIRWAYS, RESTROOMS, PRIMARY BUILDING ENTRANCE AREAS
 AND LOBBIES, AND AREAS WHERE MANUAL-ON OPERATION WOULD
 ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING
 OCCUPANTS
  
 NO OUTLETS SHOWN ON DRAWINGS
  
 FAULT CURRENT CALCULATION REQUIRED PER 110.21
  
 A/C EQUIPMENT SHOWN BUT NO ELECTRIC.