| 2017-06-22 18:06:52 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. |
| | |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND |
| | C405.2.4. |
| | |
| | C405.2.1 MANUAL LIGHTING CONTROLS. |
| | ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| | THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND |
| | C405.2.1.2. |
| | |
| | C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR |
| | THE LIGHTING SERVING THAT AREA. THE REQUIRED CONTROLS |
| | SHALL BE LOCATED WITHIN THE AREA SERVED BY THE CONTROLS |
| | OR BE A REMOTE SWITCH THAT IDENTIFIES THE LIGHTS SERVED |
| | AND INDICATES THEIR STATUS. |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND |
| | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET |
| | (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT |
| | PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE |
| | INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 |
| | MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL |
| | EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 |
| | PERCENT POWER. |
| | |
| | EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE |
| | PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS, |
| | STAIRWAYS, RESTROOMS, PRIMARY BUILDING ENTRANCE AREAS |
| | AND LOBBIES, AND AREAS WHERE MANUAL-ON OPERATION WOULD |
| | ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING |
| | OCCUPANTS |
| | |
| | NO OUTLETS SHOWN ON DRAWINGS |
| | |
| | FAULT CURRENT CALCULATION REQUIRED PER 110.21 |
| | |
| | A/C EQUIPMENT SHOWN BUT NO ELECTRIC. |