| 2017-06-30 09:15:44 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE GROUNDING ELECTRODE SYSTEM FOR MAIN HOUSE AS |
| | REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A |
| | FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 2. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL A |
| | TO CWP IS INCORRECT IN SIZE AND LOCATION. ALL GROUNDING |
| | ELECTRODE CONDUCTORS MUST ATTACH TO THE GROUNDED |
| | SERVICE CONDUCTOR ON THE SUPPLY SIDE OF THE SERVICE AND |
| | SHALL BE SIZED PER NEC 250.66. NEC 250.64(D)(3); FBC |
| | RE3607.1 |
| | 3. #6 GROUNDING ELECTRODE CONDUCTOR SHOWN FROM PANEL B |
| | TO CWP IS INCORRECT IN SIZE. GEC MUST BE SIZED PER NEC |
| | 250.66. ADDITIONALLY, ALL GROUNDING ELECTRODES PRESENT |
| | MUST BE BONDED TOGETHER, NOT JUST THE CWP. SEE COMMENT |
| | #1 ALSO. NEC 250.50; FBC RE3608.1 |
| | 4. PROVIDE FEEDER INFORMATION, WIRE AND BREAKER SIZE |
| | FOR PANEL C. NEC 215.5 |
| | 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 6. PANEL B, CIRCUITS 2,4 AND 6,8 AND 10,12 SHOW A #6 |
| | ROMEX WIRE ON A 60 AMP BREAKER. #6 WIRE IS NOT RATED |
| | FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC |
| | RE3705.4.4 |
| | 7. PANEL C, CIRCUIT 2,4 SHOW A #6 ROMEX WIRE ON A 60 |
| | AMP BREAKER. #6 WIRE IS NOT RATED FOR 60 AMPS. PROVIDE |
| | CORRECTION. NEC 334.80; FBC RE3705.4.4 |
| | 8. NOTE ON RISER DIAGRAM STATES "PER 2008 NEC". CORRECT |
| | TO CURRENT CODE, 2011 NEC. FBC PREFACE |
| | 9. PROVIDE 20 AMP CIRCUIT FOR BATH GFCI OUTLETS. A |
| | MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11(C)(3) |
| | , FBC RE3703.4 |
| | 10. GARAGE BUILDING, 2ND FLOOR BEDROOM DOES NOT SHOW A |
| | SMOKE ALARM. ADDITIONALLY, THE COMBO SMOKE/CO ALARM IS |
| | REQUIRED TO BE WITHIN 10 FEET OF BEDROOM. ADDITIONALLY, |
| | A SMOKE ALARM IS REQUIRED ON EACH LEVEL OF THE BUILDING |
| | AND THERE IS NOT ONE SHOWN ON 1ST FLOOR PLAN. PROVIDE |
| | CORRECTION. FBC R314, R315 |
| | 11. GARAGE BUILDING, BEDROOM CLOSET SHOWS A RECESS |
| | LIGHT. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| | AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 12. MASTER CLOSETS SHOW RECESS LIGHTS. LIGHTING WITH |
| | OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES |
| | OR LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS. |
| | PROVIDE CORRECTION. NEC 410.16(B), FBC RE4003.12 |
| | 13. MASTER BATH SHOWS A RECESS LIGHT ABOVE TUB. |
| | LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| | FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A), |
| | FBC RE4003.11 |
| | 14. OUTDOOR RECESS LIGHTS IN PORCH AND COVERED WALKWAY |
| | AREAS ARE REQUIRED TO BE SUITABLE FOR DAMP LOCATIONS. |
| | PROVIDE NOTE TO COMPLY. NEC 410.10(A), FBC RE4003.11 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |