| 2017-07-05 14:46:47 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL 2ND REVIEW COMMENTS: |
| | |
| | 1. PREVIOUS COMMENT NOT ADDRESSED: "NO ELECTRICAL PLAN |
| | PROVIDED FOR REVIEW. PROVIDE PLAN SHOWING ALL |
| | ELECTRICAL WORK". WITH EACH APPLICATION, THERE ARE |
| | SEVERAL DIFFERENT FLOOR LAYOUTS. REMOVE ANY ITEMS NOT |
| | RELATED TO THE UNIT IN QUESTION AND PROVIDE ELECTRICAL |
| | PLAN SHOWING WHICH FIXTURES WILL BE |
| | REMOVED/REPLACED/INSTALLED. ELECTRICAL PLAN IS REQUIRED |
| | TO BE SIGNED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC |
| | 107.3.5 |
| | 2. PREVIOUS COMMENT NOT ADDRESSED: "PROVIDE COPY OF |
| | CONTRACT SHOWING TOTAL COST OF JOB, TO INCLUDE LABOR |
| | AND MATERIALS". PROVIDING AN UNSIGNED CONTRACT WITH A |
| | PER FIXTURE PRICE IS NOT ACCEPTABLE. PROVIDE TOTAL |
| | VALUE OF JOB FOR EACH UNIT, INCLUDING LABOR AND COST OF |
| | FIXTURES. PROVIDE SPEC SHEET OF LIGHT FIXTURES. NEC |
| | 110.3; FBC 109.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |