| Plan Review Notes For Permit 17060552 |
| Permit Number |
17060552 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-08-08 12:02:08 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060552 | | | 8/8/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENTS #1 & 2 FROM THE PREVIOUS REVIEW STILL EXIST. I | | | AM REPRINTING THEM BELOW WITH AN ADDITIONAL COMMENT | | | BASED ON THE NEW ENERGY COMPLIANCE FORM. | | | | | | 1) THE EQUIPMENT SCHEDULE ON THE PLAN AND THE AHRI | | | CERTIFICATE INDICATE A 2-TON SYSTEM, HOWEVER THE PLAN | | | IS INDICATING 1065 CFMS OF SUPPLY AIR. THAT AMOUNT OF | | | AIR WOULD TYPICALLY EXCEED THE CAPACITY OF THE 2-TON | | | SYSTEM. IT MAY BE POSSIBLE THAT THE WRONG SCHEDULE WAS | | | PLACED ON THE PLAN, AND THE WRONG AHRI CERTIFICATE | | | SUBMITTED. PLEASE CORRECT AND REMOVE OR MARK VOID ON | | | ALL SHEETS IN THE PERMIT FILE THAT ARE NO LONGER | | | APPLICABLE TO THE PROJECT. | | | | | | 2) INDICATE ON THE SUBMITTED PLAN THE MINIMUM WORKING | | | CLEARANCE SPACE FOR THE NEW AIR HANDLER IN THE CLOSET- | | | 3 INCHES ALONG THE SIDES, BACK, AND TOP WITH A TOTAL | | | WIDTH OF THE CLOSET AT LEAST 12 INCHES WIDER THAN THE | | | AIR HANDLER- SECTION M1305.1.1 FBC-14 RESIDENTIAL. | | | | | | 3) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION | | | COMPONENT CRITERIA CHECKLIST SUBMITTED WITH FORM | | | R405-2014. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|