2017-08-08 12:02:083RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17060552
 8/8/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1 & 2 FROM THE PREVIOUS REVIEW STILL EXIST. I
 AM REPRINTING THEM BELOW WITH AN ADDITIONAL COMMENT
 BASED ON THE NEW ENERGY COMPLIANCE FORM.
  
 1) THE EQUIPMENT SCHEDULE ON THE PLAN AND THE AHRI
 CERTIFICATE INDICATE A 2-TON SYSTEM, HOWEVER THE PLAN
 IS INDICATING 1065 CFMS OF SUPPLY AIR. THAT AMOUNT OF
 AIR WOULD TYPICALLY EXCEED THE CAPACITY OF THE 2-TON
 SYSTEM. IT MAY BE POSSIBLE THAT THE WRONG SCHEDULE WAS
 PLACED ON THE PLAN, AND THE WRONG AHRI CERTIFICATE
 SUBMITTED. PLEASE CORRECT AND REMOVE OR MARK VOID ON
 ALL SHEETS IN THE PERMIT FILE THAT ARE NO LONGER
 APPLICABLE TO THE PROJECT.
  
 2) INDICATE ON THE SUBMITTED PLAN THE MINIMUM WORKING
 CLEARANCE SPACE FOR THE NEW AIR HANDLER IN THE CLOSET-
 3 INCHES ALONG THE SIDES, BACK, AND TOP WITH A TOTAL
 WIDTH OF THE CLOSET AT LEAST 12 INCHES WIDER THAN THE
 AIR HANDLER- SECTION M1305.1.1 FBC-14 RESIDENTIAL.
  
 3) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 COMPONENT CRITERIA CHECKLIST SUBMITTED WITH FORM
 R405-2014.
  