| 2017-07-13 15:30:44 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060552 |
| | 7/13/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE EQUIPMENT SCHEDULE ON THE PLAN AND THE AHRI |
| | CERTIFICATE INDICATE A 2-TON SYSTEM, HOWEVER THE PLAN |
| | IS INDICATING 1065 CFMS OF SUPPLY AIR. THAT AMOUNT OF |
| | AIR WOULD TYPICALLY EXCEED THE CAPACITY OF THE 2-TON |
| | SYSTEM. IT MAY BE POSSIBLE THAT THE WRONG SCHEDULE WAS |
| | PLACED ON THE PLAN, AND THE WRONG AHRI CERTIFICATE |
| | SUBMITTED. PLEASE CORRECT AND REMOVE OR MARK VOID ON |
| | ALL SHEETS IN THE PERMIT FILE THAT ARE NO LONGER |
| | APPLICABLE TO THE PROJECT. |
| | |
| | 2) INDICATE ON THE SUBMITTED PLAN THE MINIMUM WORKING |
| | CLEARANCE SPACE FOR THE NEW AIR HANDLER IN THE CLOSET- |
| | 3 INCHES ALONG THE SIDES, BACK, AND TOP WITH A TOTAL |
| | WIDTH OF THE CLOSET AT LEAST 12 INCHES WIDER THAN THE |
| | AIR HANDLER- SECTION M1305.1.1 FBC-14 RESIDENTIAL. |
| | |
| | 3) CLARIFY WHAT THE 20" LABEL IN THE KITCHEN IS |
| | IDENTIFYING- A DUCT, A GRILL? |
| | |
| | 4) PROVIDE TWO COMPLETE AND CLEAR, LEGIBLE COPIES OF |
| | THE FL. PRODUCT APPROVAL #14239-R3. THE DOCUMENT |
| | SUBMITTED IS MISSING PAGES 2 & 4 AND HAS FAINT |
| | ILLEGIBLE PRINT. PLEASE NOTE THAT THE REQUIRED |
| | STRUCTURAL DETAILS FOR THE CONDENSER MOUNTING PAD ARE |
| | CONTAINED IN NOTE #7 ON PAGE 1. |
| | |
| | 5) COMMENT #2 FROM THE PREVIOUS REVIEW STILL EXISTS. I |
| | HAVE REPRINTED THE COMMENT BELOW- PLEASE COMPLY. |
| | |
| | 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY |
| | CONSERVATION: THE PREVIOUSLY UNCONDITIONED GARAGE |
| | APARTMENT MUST BE BROUGHT INTO FULL COMPLIANCE WITH THE |
| | CODE, THEREFORE THE SUBMITTED ENERGY FORM R402-2014 IS |
| | INCOMPLETE, AND ALSO INVALID. PLEASE READ THE "SCOPE" |
| | AT THE TOP OF THE FORM: "TO COMPLY, A BUILDING MUST |
| | MEET OR EXCEED ALL OF THE ENERGY EFFICIENCY |
| | REQUIREMENTS ON |
| | |
| | TABLE R402A AND ALL APPLICABLE MANDATORY REQUIREMENTS |
| | SUMMARIZED INTABLE R402B OF THIS FORM...." |
| | |