| Plan Review Notes For Permit 17060532 |
| Permit Number |
17060532 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-15 11:37:22 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060532 | | | 6/15/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE AC CONTRACTOR WHO PREPARED THE REVISED | | | MECHANICAL PLAN SHALL SUBMIT A SUB-PERMIT APPLICATION | | | AS REQUIRED BY SECTION 105.3.1.2 ITEM #3 WPB AMENDMENTS | | | TO THE FBC-10 BUILDING. | | | | | | 2) THE ENGINEER OF RECORD MAURICE EVAN LORD PE WHO DID | | | THE ORIGINAL MECHANICAL DESIGN ON SHEET E-1 MUST | | | PROVIDE REVISED ELECTRICAL PLANS TO ACCOMODATE THE NEW | | | AC SYSTEM. BECAUSE LORD IS STILL THE MECHANICAL | | | DESIGNER OF RECORD, HE MUST REVIEW AND APPROVE THE NEW | | | AC DRAWINGS. | | | | | | 3) REFER TO SECTION 602.1: THE NEW AC CLOSETS ARE | | | PLENUM ENCLOSURES AND MUST BE CONTRUCTED IN ACCORDANCE | | | WITH SECTION 602.2. PLEASE NOTE NON-COMBUSTIBLE CLOSET | | | DOORS ARE REQUIRED. | | | | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CONDENSATE PUMPS. | | | | | | 5) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE | | | CONDENSER TIE DOWN CLIPS AND LIST THE NOA NUMBER BY THE | | | CONDENSER DETAIL ON SHEET M.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|