| 2017-07-18 14:06:43 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ARCHITECT OF RECORD TO COORDINATE A/C PLAN WITH |
| | EQUIPMENT SIZING CALCULATIONS SUBMITTED. CFM'S DON'T |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ARCHITECT TO SPECIFY ON THE A/C PLAN THE CFM'S FOR |
| | THE EXISTING LIVING ROOM. SEC. 107.3.5.3(10) CITY |
| | AMENDMENTS. |
| | |
| | 3- ARCHITECT TO SPECIFY ON PLANS THE EQUIPMENT |
| | MANUFACTURER AND MODEL #. SEC. 107.3.5.3(10) CITY |
| | AMENDMENTS. COORDINATE WITH THE EQUIPMENT SIZING |
| | CALCULATIONS SUBMITTED. |
| | |
| | 4- ARCHITECT TO CLARIFY WHY THE RETURN AIR DUCTWORK IS |
| | CONNECTED TO THE DISCONNECT?. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- ARCHITECT TO SPECIFY ON A/C PLAN COMPLIANCE WITH THE |
| | BALANCED RETURN AIR FOR THE NEW FAMILY ROOM AS REQUIRED |
| | BY SEC. M1602.4 FBC-RESIDENTIAL. |
| | |
| | 6- PERSON PREPARING THE EQUIPMENT SIZING CALCULATIONS |
| | TO CLARIFY WHY SPECIFYING 10 PEOPLE FOR A 3 BEDROOM |
| | HOUSE. TYPICALLY A 3 BEDROOM HOUSE DOESN'T HAVE 10 |
| | OCCUPANTS. NUMBER OF OCCUPANTS MAY AFFECT THE SIZING OF |
| | THE EQUIPMENT. EQUIPMENT SIZING SHALL BE DONE BASED ON |
| | THE ACTUAL NUMBER OF PEOPLE. PROVIDE JUSTIFICATIONS OF |
| | WHY 10 PEOPLE. CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 7- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE |
| | INCOMPLETE. NEED TO PROVIDE COMPLETE INFORMATION FOR |
| | THE EQUIPMENT. COORDINATE WITH ARCHITECT'S A/C PLAN. |
| | ALSO, SEE ARCHITECT'S A/C PLAN FOR CORRECT FLOOR LAYOUT |
| | AND LOCATION OF REGISTERS. SEC. 107.3.5.3(10) CITY |
| | AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS WITH NEW SET OF |
| | PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |