| Plan Review Notes For Permit 17060525 |
| Permit Number |
17060525 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-22 19:26:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROPOSED POOL IS LOCATED IN AN AREA OF | | | QUESTIONABLE SOILS. SUBMIT TWO COPIES OF A SIGNED AND | | | SEALED GEOTECHNICAL EVALUATION PERSUANT TO FBC-R401.4 | | | FOR THE PROPOSED POOL. SUBMIT TWO SETS OF SIGNED AND | | | SEALED ENGINEERED DESIGN DRAWINGS FOR THE POOL | | | FOUNDATION BASED ON THE RECOMMEDATIONS OF THE SOIL | | | REPORT . FBC 107.2.1.3 | | | | | | 2) THE PROPOSED POOL IS LOCATED IN A SPECIAL FLOOD | | | HAZARD AREA. THE POOL EQUIPMENT IS REQUIRED TO BE | | | LOCATED ONE FOOT ABOVE THE BASE FLOOD ELEVATION. | | | THEREFORE, THE EQUIPMENT IS REQUIRED TO BE 8 FT NGVD OR | | | HIGHER. FBC-R322.1.6 | | | | | | 3) A POOL PLUMBING SUB-PERMIT IS REQUIRED IN ORDER TO | | | BE ABLE TO SCHEDULE THE POOL PIPING INSPECTIONS. SUBMIT | | | AN APPLICATION FOR THE POOL PLUMBING SUB PERMIT. FBC | | | 105 |
|