| 2017-06-19 08:20:04 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. IDENTIFY UNDERLAYMENT TO BE INSTALLED. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2. PROVIDE TEST REPORTS FOR ASTM E-90, E-492 & E-84 FOR |
| | THE PROPOSED UNDERLAYMENT FOR THE EXISTING SITE |
| | CONDITIONS. |
| | |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84 |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3. ALL SUBMITTAL DOCUMENTS SHALL BE IN DUPL;ICATE. |
| | |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |