| 2017-07-18 16:04:43 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SPECIFY THE DIMENSIONS OF THE PROPOSED BATHROOM FROM |
| | THE EXTERIOR WALL AT THE TUB TO THE INTERIOR WALL AT |
| | THE FAMILY ROOM. FBC 107.2.1 |
| | |
| | 2) THE WINDOW IN THE PROPOSED BATHROOM WILL HAVE TO |
| | COMPLY WITH FBC - R308.4.5 FOR SAFETY GLAZING. R308.4.5 |
| | GLAZING IN WALLS, ENCLOSURES OR FENCES CONTAINING OR |
| | FACING HOT TUBS, SPAS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, |
| | BATHTUBS, SHOWERS AND INDOOR OR OUTDOOR SWIMMING POOLS |
| | WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS |
| | THAN 60 INCHES (1524 MM) MEASURED VERTICALLY ABOVE ANY |
| | STANDING OR WALKING SURFACE SHALL BE CONSIDERED A |
| | HAZARDOUS LOCATION. THIS SHALL APPLY TO SINGLE GLAZING |
| | AND ALL PANES IN MULTIPLE GLAZING. IF THE EXISTING |
| | WINDOW HAS TO BE REPLACED, SUBMIT TWO SETS OF PRODUCT |
| | APPROVALS FOR THE NEW WINDOW. FBC 107.3.4.1 |
| | |
| | 3) WALL SECTION "A" SHOWS A NEW 5 INCH CONCRETE SLAB |
| | POURED OVER THE EXISTING SLAB. THE OTHER DRAWINGS |
| | SPECIFY A NEW 4 INCH CONCRETE SLAB OVER THE EXISTING |
| | ONE. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 4) IN ADDITION TO THE EXISTING ATTIC SPACE, THE 2014 |
| | FBC ENERGY CONSERVATION CODE REQUIRES THE EXISTING |
| | CONCRETE BLOCK EXTERIOR WALLS TO BE INSULATED. SPECIFY |
| | THE CBS WALL INSULATION ON THE PLANS. FBC ENERGY |
| | SECTION R402.1 |
| | |
| | 5) SUBMIT THE REQUIRED FORMS AND MATERIALS TO SHOW THAT |
| | THE PROPOSED WORK COMPLIES WITH THE FBC ENERGY CODE. |
| | SEE FBC ENERGY CONSERVATION CODE SECTION R101.5.1 |