Plan Review Notes
Plan Review Notes For Permit 17060481
Permit Number 17060481
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-28 10:29:51CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE 2 COPIES OF PLAN FOR REVIEW. FBC 107.1
 2. PROVIDE EXISTING FLOOR PLAN SHOWING LOCATION OF ALL
 SMOKE/CO ALARMS IN RESIDENCE. IF NONE ARE EXISTING, OR
 NOT TO CODE, SHOW AS NEW INSTALLATIONS WITH
 INTERCONNECTION AS REQUIRED PER CODE. FBC R314, R315.
 FBC 107.2.1
 3. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED
 CIRCUITS, WITH AFCI OR GFCI PROTECTION PER CODE. NEC
 408.4, 215.5; FBC 107.2.1
 4. PROVIDE SWITCHED LIGHT FOR EXTERIOR DOOR IF NOT
 THERE ALREADY (NOT SHOWN ON PLAN). FOR DWELLING UNITS,
 ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC
 POWER, AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE OF
 OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. NEC
 210.70(A)(2)(B), FBC RE3903.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  