| Plan Review Notes For Permit 17060447 |
| Permit Number |
17060447 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-17 12:24:44 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. HORIZONTAL DRY VENTS ARE NOT ALLOWED PLEASE REMOVE | | | THEM FROM THE WC IN POWDER ROOM BATH, THE SHOWER IN | | | BATH#4 THE WC IN MASTER BATH, THE SHOWER IN BATH #2 AND | | | THE WC IN BATH #3. PER FBC RES P3104.3, P3104.4 | | | | | | 2.IN BATH #3 THE LAV SHALL CONNECT TO THE BRANCH DRAIN | | | BETWEEN THE TUB AND WC TO CREATE A CODE COMPLAINT WET | | | VENT SYSTEM PER FBC RES P3108.1 | | | | | | 3.IN THE MASTER BATH THE LAV SHALL CONNECT TO THE | | | BRANCH DRAIN BETWEEN THE SHOWER AND WC TO CREATE A CODE | | | COMPLAINT WET VENT SYSTEM PER FBC RES P3108.1 | | | | | | 4. FBC RES P3005.2.6 BASE OF STACKS. | | | A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE | | | OR SOIL STACK. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|