Plan Review Notes
Plan Review Notes For Permit 17060447
Permit Number 17060447
Review Stop P
Sequence Number 2
Notes
Date Text
2017-08-17 12:24:442ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. HORIZONTAL DRY VENTS ARE NOT ALLOWED PLEASE REMOVE
 THEM FROM THE WC IN POWDER ROOM BATH, THE SHOWER IN
 BATH#4 THE WC IN MASTER BATH, THE SHOWER IN BATH #2 AND
 THE WC IN BATH #3. PER FBC RES P3104.3, P3104.4
  
 2.IN BATH #3 THE LAV SHALL CONNECT TO THE BRANCH DRAIN
 BETWEEN THE TUB AND WC TO CREATE A CODE COMPLAINT WET
 VENT SYSTEM PER FBC RES P3108.1
  
 3.IN THE MASTER BATH THE LAV SHALL CONNECT TO THE
 BRANCH DRAIN BETWEEN THE SHOWER AND WC TO CREATE A CODE
 COMPLAINT WET VENT SYSTEM PER FBC RES P3108.1
  
 4. FBC RES P3005.2.6 BASE OF STACKS.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  