| 2017-06-14 10:10:32 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PANEL A, CIRCUIT 16 SHOWS A 15 AMP CIRCUIT WITH #14 |
| | WIRE TO THE BATHROOM OUTLETS. PROVIDE CORRECTION. "A |
| | MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS." NEC 210.11(C)(3) |
| | , FBC RE3703.4 |
| | 2. BASED ON THE INFORMATION PROVIDED ON THE MECHANICAL |
| | PLAN, THE AHU'S HAVE A 15 KW HEAT STRIP, AND THIS |
| | CIRCUIT IS FED FROM A 60 AMP BREAKER WITH #6 WIRE. IT |
| | APPEARS THAT THE WIRE SIZE AND BREAKER SIZE ARE LESS |
| | THAN THE MINIMUM CIRCUIT AMPACITY REQUIRED. PROVIDE |
| | CORRECTION. FBC RE3702.7, 3702.11, NEC 440.35 |
| | 3. PROVIDE NOTE ON PLAN THAT THE GENERATOR WILL BE |
| | UNDER SEPARATE PERMIT. FBC 107.2.1 |
| | 4. PROVIDE SPEC SHEET FOR 300 AMP TRANSFER SWITCH |
| | INDICATED AT SERVICE. PROVIDE DETAILS FOR LOAD |
| | MANAGEMENT PER NEC. NEC 110.3, 702.4(B)(2) |
| | 5. ALTHOUGH GENERATOR WILL BE UNDER SEPARATE PERMIT, IT |
| | APPEARS THAT THE 3 FOOT CLEARANCE REQUIREMENTS WILL NOT |
| | BE MET WITH THE CURRENT DESIGN OF THE EQUIPMENT GARAGE. |
| | PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26 |
| | 6. SEVERAL LOCATION ON PLANS SHOW A DECORATIVE SCONCE |
| | IN CLOSETS. PROVIDE CORRECTION. "LIGHTING WITH OPEN OR |
| | PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR |
| | LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS." NEC |
| | 410.16(B), FBC RE4003.12 |
| | 7. LIGHTING IN "HER MASTER CLOSET" IS SHOWN WITH |
| | STANDARD RECESS LIGHTS. "LIGHTING WITH OPEN OR |
| | PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR |
| | LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS". PROVIDE |
| | CORRECTION. NEC 410.16(B), FBC RE4003.12 |
| | 8. SMOKE ALARM REQUIRED AT BOTTOM OF STAIRS. PROVIDE |
| | CORRECTION. FBC R314.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |