Plan Review Notes
Plan Review Notes For Permit 17060447
Permit Number 17060447
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-14 10:10:32CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PANEL A, CIRCUIT 16 SHOWS A 15 AMP CIRCUIT WITH #14
 WIRE TO THE BATHROOM OUTLETS. PROVIDE CORRECTION. "A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS." NEC 210.11(C)(3)
 , FBC RE3703.4
 2. BASED ON THE INFORMATION PROVIDED ON THE MECHANICAL
 PLAN, THE AHU'S HAVE A 15 KW HEAT STRIP, AND THIS
 CIRCUIT IS FED FROM A 60 AMP BREAKER WITH #6 WIRE. IT
 APPEARS THAT THE WIRE SIZE AND BREAKER SIZE ARE LESS
 THAN THE MINIMUM CIRCUIT AMPACITY REQUIRED. PROVIDE
 CORRECTION. FBC RE3702.7, 3702.11, NEC 440.35
 3. PROVIDE NOTE ON PLAN THAT THE GENERATOR WILL BE
 UNDER SEPARATE PERMIT. FBC 107.2.1
 4. PROVIDE SPEC SHEET FOR 300 AMP TRANSFER SWITCH
 INDICATED AT SERVICE. PROVIDE DETAILS FOR LOAD
 MANAGEMENT PER NEC. NEC 110.3, 702.4(B)(2)
 5. ALTHOUGH GENERATOR WILL BE UNDER SEPARATE PERMIT, IT
 APPEARS THAT THE 3 FOOT CLEARANCE REQUIREMENTS WILL NOT
 BE MET WITH THE CURRENT DESIGN OF THE EQUIPMENT GARAGE.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26
 6. SEVERAL LOCATION ON PLANS SHOW A DECORATIVE SCONCE
 IN CLOSETS. PROVIDE CORRECTION. "LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS." NEC
 410.16(B), FBC RE4003.12
 7. LIGHTING IN "HER MASTER CLOSET" IS SHOWN WITH
 STANDARD RECESS LIGHTS. "LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOSETS". PROVIDE
 CORRECTION. NEC 410.16(B), FBC RE4003.12
 8. SMOKE ALARM REQUIRED AT BOTTOM OF STAIRS. PROVIDE
 CORRECTION. FBC R314.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  