| 2017-08-08 11:27:21 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060431 |
| | 8/8/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENT #1 FROM THE PREVIOUS REVIEW STILL EXISTS. I AM |
| | REPRINTING IT BELOW WITH ADDITONAL COMMENTS BASED ON |
| | THE RESUBMITTED DOCUMENTS. |
| | |
| | 1) IT APPEARS THAT ONE SET OF NEW AC PLANS FOR THE |
| | GARAGE APARTMENTS WAS NOT SUBMITTED. THE PERMIT |
| | APPLICATION INDICATES A 2.5 TON AND A 2-TON SYSTEM TO |
| | BE INSTALLED, HOWEVER ONLY ONE OF PLANS FOR THE 2.5 TON |
| | SYSTEM WAS SUBMITTED. ADDITIONALLY THE 2.5 TON SYSTEM |
| | SPECIFIED APPEARS TO BE OVERSIZED FOR THE APARTMENT, OR |
| | POSSIBLY, THE WRONG EQUIPMENT SCHEDULE WAS WRITTEN ON |
| | THE PLAN. PLEASE CORRECT AND REMOVE OR MARK VOID ON ALL |
| | SHEETS IN THE PERMIT FILE THAT ARE NO LONGER APPLICABLE |
| | TO THE PROJECT. |
| | |
| | 2) REFER TO TABLE R301.1 FBC-14 ENERGY CONSERVATION AND |
| | PROVIDE THE CORRECT CLIMATE ZONE NUMBER FOR PALM BEACH |
| | COUNTY ON THE ENERGY FORM R405-2014: 1A. |
| | |
| | 3) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION |
| | COMPONENT CRITERIA CHECKLIST SUBMITTED WITH FORM |
| | R405-2014. |
| | |
| | 4) THE DIRECTIONAL ORIENTATION OF THE GARAGE APARTMENT |
| | SHOWN ON THE WRIGHTSOFT AC CALCULATION INDICATES THE |
| | FRONT DOOR FACES EAST, HOWEVER THE FRONT DOOR AS SHOWN |
| | ON THE GIS APPEARS TO BE FACING WEST. PLEASE CORRECT |
| | THE AC CALCULATIONS AND THE ENERGY FORM R405-2014 WHICH |
| | SHOWS INCORRECT WINDOW ORIENTATIONS AND INCORRECT |
| | NUMBERS OF WINDOWS WHEN COMPARED WITH THE |
| | |
| | AC PLAN. |
| | |