Plan Review Notes
Plan Review Notes For Permit 17060431
Permit Number 17060431
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-19 10:11:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060431
 6/19/17
  
 RESULTS: DENIED.
  
 1) THE COMPANY THAT PREPARED THE AC AND ENERGY
 CALCULATIONS- ENERGY HOUSE TECHNOLOGY- CANNOT DRAW THE
 AC PLAN FOR THE MAIN HOUSE AND THE GARAGE APARTMENT
 UNLESS THE COMPANY IS FL. STATE LICENSED AS AN AC OR
 MECHANICAL CONTRACTOR, AND IS THE INSTALLING CONTRACTOR
 ON THE PROJECT- SECTIION 105.3.1 WEST PALM BEACH
 AMENDMENTS TO THE FBC.
  
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: THE PREVIOUSLY UNCONDITIONED GARAGE
 APARTMENT MUST BE BROUGHT INTO FULL COMPLIANCE WITH THE
 CODE, THEREFORE THE SUBMITTED ENERGY FORM R402-2014 IS
 INCOMPLETE, AND ALSO INVALID. PLEASE READ THE "SCOPE"
 AT THE TOP OF THE FORM: "TO COMPLY, A BUILDING MUST
 MEET OR EXCEED ALL OF THE ENERGY EFFICIENCY
 REQUIREMENTS ON
  
 TABLE R402A AND ALL APPLICABLE MANDATORY REQUIREMENTS
 SUMMARIZED INTABLE R402B OF THIS FORM...."
  