Plan Review Notes
Plan Review Notes For Permit 17060411
Permit Number 17060411
Review Stop E
Sequence Number 2
Notes
Date Text
2017-08-22 15:21:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT REFERENCING THE DISCONNECTS
 REQUIRED FOR SEPARATE STRUCTURES WAS NOT ADDRESSED
 SATISFACTORILY. BASED ON THE CURRENT RISER DIAGRAM
 PROVIDED, PANELS A, A2, B, AND P ARE ALL FED FROM
 SEPARATE STRUCTURES AND WOULD REQUIRE A MAIN BREAKER OR
 A DISCONNECT AT THE LOCATION OF THE PANEL REMOTE FROM
 THE SEPARATE STRUCTURE. PROVIDE CORRECTION. PLEASE FEEL
 FREE TO CALL REVIEWER IF YOU HAVE ANY QUESTIONS. NEC
 225.30
 2. PREVIOUS COMMENT REFERENCING THE GROUNDING ELECTRODE
 (GE) SYSTEM REQUIRED FOR SEPARATE STRUCTURES WAS NOT
 ADDRESSED SATISFACTORILY. PROVIDE A GE SYSTEM AT EACH
 STRUCTURE AND SHOW THE PROPER SIZE WIRE FROM EACH PANEL
 TO THAT SYSTEM AND THE WIRE THAT TIES BOTH SYSTEMS
 TOGETHER THAT IS REQUIRED PER CODE. NEC 250.32; FBC
 RE3607.3
 3. GENERATOR SHOWS 3 - 4/0 AL CONDUCTORS RUNNING TO
 MAIN DISC. A. WHAT IS THIS WIRE FOR? THE GENERATOR FEED
 SHOULD ONLY BE RUN TO THE TRANSFER SWITCH. PROVIDE
 CORRECTION. NEC 702.5, NEC 110.3; FBC 107.2.1
 4. GENERATOR TRANSFER SWITCH IS SPECIFIED AS 200 AMP
 GUARDIAN MODEL. THE MAXIMUM WIRE CAPACITY FOR THIS
 TRANSFER SWITCH PER THE MANUFACTURERS SPEC SHEET IS 250
 KCMIL. RISER DIAGRAM SHOWS PARALLEL 500 KCMIL AL FROM
 GENERATOR TO TRANSFER SWITCH, AND PARALLEL 350 KCMIL
 COPPER FROM 400 AMP DISCONNECT TO TRANSFER SWITCH. WHY
 IS THERE SO MUCH WIRE TO THIS TRANSFER SWITCH, IT IS
 RATED FOR 200 AMPS? PROVIDE CORRECTION. NEC 110.3; FBC
 107.2.1
 5. RISER DIAGRAM SHOW MAIN DISC A AND MAIN DISC B.
 HOWEVER, THESE ARE NOT DISCONNECTS, THEY ARE FEED THRU
 PANELS. PROVIDE PANEL SCHEDULES FOR EACH OF THESE
 PANELS. AS A SIDE NOTE, IT WOULD MAKE MORE SENSE TO
 FEED PANEL P AND PANEL A2 FROM THEIR RESPECTIVE MAIN
 PANELS INSTEAD OF RUNNING A FEED ALL THE WAY TO THE
 MAIN HOUSE AND THEN BACK TO THESE PANELS. RISER DIAGRAM
 NEEDS TO REFLECT THE ACCURATE INSTALLATION. PROVIDE
 CORRECTIONS AS NOTED AND PROVIDE UPDATED RISER DIAGRAM.
 NEC 215.5, 230, 250.50, 250.94, 408.30 FBC RE3706.1,
 RE3608.1, RE3609.3; FBC 107.2.1
 6. WIRE SIZE SHOWN ON RISER DIAGRAM FROM MAIN
 DISCONNECTS (PANELS) A & B TO THE RESPECTIVE INTERIOR
 PANEL IS NOT SIZED PROPERLY. SIZE 2/0 CAN ONLY BE USED
 WHERE IT FEED 100% OF THE LOAD. SINCE THE MAINS ARE
 FEED THRU PANELS, THE WIRE SIZE TO INTERIOR PANELS WILL
 NEED TO BE INCREASED. NEC 310.15(B)(7); FBC RE3602.2
 7. CO ALARMS ARE REQUIRED WITHIN 10 FEET OF SLEEPING
 ROOMS. PROVIDE CORRECTION. FBC R315.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  