Plan Review Notes
Plan Review Notes For Permit 17060411
Permit Number 17060411
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2017-07-18 10:38:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC R = FBC 2014 RESIDENTIAL
  
 DFE PROPOSED NOT CLEAR. PLAN PROPOSES 8', SITE PLAN
 (SURVEY) PROPOSES 9.17.
  
 1. PLEASE SEE FBC R 322.1.4, ESTABLISHING THE DESIGN
 FLOOD ELEVATION. RECAP OF THIS SECTION (SEE ACTUAL CODE
 FOR FULL TEXT):
  
 THE DESIGN FLOOD ELEVATION SHALL BE USED TO DEFINE
 FLOOD HAZARD AREAS. AT A MINIMUM, THE DESIGN FLOOD
 ELEVATION IS THE HIGHER OF:
  
 THE BASE FLOOD ELEVATIN AT THE DEPTH OF PEAK ELEVATION
 OF FLOODING (INCLUDING WAVE HEIGHT) WHICH HAS A 1% OR
 GREATER CHANCE OF BEING EQUALED OR EXCEEDED IN ANY
 GIVEN YEAR, OR
  
 THE ELEVATION OF THE DESIGN FLOOD ASSOCIATED WITH THE
 AREA DESIGNATED ON A FLOOD HAZARD MAP ADOPTED BY THE
 COMMUNITY, OR OTHERWISE LEGALLY DESIGNATED.
  
 2. PLEASE ALSO SEE FBC R 322.2.1 WHICH ADDRESSES
 ELEVATION REQUIREMENTS FOR THE LOWEST FLOOR (AKA FFE),
 R322.1.6 FOR MECHANICAL/ELECTRICAL/PLUMBING SYSTEMS.
  
 3. PLEASE SEE THE PRELIMINARY MAP (AVAILABLE AT FEMA
 MAP SERVICE CENTER) AND THE NEW FLOOD INSURANCE STUDY.
 A "LETTER OF FINAL DETERMINATION" WAS GIVEN FROM FEMA
 TO THE CITY IN APRIL, 2017. ALTHOUGH THE INSURANCE MAP
 (FIRM) HAS AN EFFECTIVE DATE OF OCTOBER 5, 2017, THE
 DATA IN THE FLOOD INSURANCE STUDY (FIS), IN CONJUCTION
 WITH THE FLOOD INSURANCE RATE MAP (FIRM) IS CONSIDERED
 DATA WHICH SHOULD BE USED TO DETERMINE DESIGN FLOOD
 ELEVATION FOR CONSTRUCTION PURPOSES.
  
 PLEASE SEE PRELIMINARY FLOOD INSURANCE RATE MAP PANEL
 12099C0591F. THIS PARCEL IS LOCATED IN SFHA AE. ON THE
 FIRM, THE EASTERN PORTION OF THE PARCEL HAS A BFE OF
 7.0 NAVD88. THE WESTERN PORTION OF THE PARCEL HAS A BFE
 OF 6.0. THE STRUCTURE PROPOSED APPEARS TO BE IN BOTH.
  
 SEE FIRM "NOTES TO USERS" - THE FLOOD INSURANCE STUDY
 IS TO BE USED (IN CONJUNCTION WITH THE FIRM) TO
 DETERMINE THE BFE.
  
 POTTER ROAD IS LOCATED BETWEEN TRANSECTS 12 AND 13.
 THEREFORE, PLEASE CONSIDER THE FOLLOWING DATA TO
 DETERMINE THE BFE:
  
 TRANSECT 12, STILLWATER 1%: 5.7' NAVD88 WAVE CREST 1%:
 7.8' NAVD88
 TRANSECT 13, STILLWATER 1%: 5.8' NAVD88 WAVE CREST 1%:
 7.3' NAVD88
  
 THE PROPOSED FINISHED FLOOR OF 8' NGVD29 IS LOWER THAN
 THE 1% CHANGE OF FLOOD. ALTHOUGH A FREEBOARD IS NOT
 REQUIRED AT THIS TIME, A 1-2' FREEBOARD IS ENCOURAGED
 AS GOOD DESIGN PRACTICE. NOTE THAT ASCE24 (WHICH IS NOT
 REQUIRED FOR THIS PROJECT) REQUIRES A MINIMUM 1'
 FREEBOARD.
  
 PLEASE CONSIDER CONTACTING YOUR INSURANCE AGENT BEFORE
 MAKING A DECISION REGARDING FREEBOARD. PLEASE ALSO
 CONSIDER CONTACTING A SURVEYOR (OR OTHER PROFESSIONAL)
 REGARDING THE PROCESS TO OBTAIN A LOMR AFTER
 CONSTRUCTION. THIS INFORMATION MAY PROVIDE APPLICANT
 WITH INFORMATION USEFUL TO DETERMINE A DESIGN FLOOD
 ELEVATION.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 4. FBC 107, A DRAINAGE PLAN, OR GRADING PLAN, WAS NOT
 PROVIDED. IT IS NOT CLEAR WHAT IMPACT THIS IMPROVEMENT
 WILL HAVE ON THE PROPERTIES TO THE WEST AND SOUTH. IT
 IS POSSIBLE THAT CAN BE A PROVISO ITEM.
  
 PLEASE PROVIDE SPOT ELEVATIONS IF AVAILABLE. PLEASE
 FEEL FREE TO CONTACT ME TO DISCUSS.
  
 5. IN ORDER TO EXPEDITE PLAN REVIEWS FOR THIS PROJECT,
 IT IS SUGGESTED THAT THE DRIVEWAY PERMIT BE REMOVED
 FROM THIS APPLICATION PACKAGE AND BE SUBMITTED
 SEPARATELY. OTHERWISE, THE HOUSE PERMIT APPLICATION
 (17060411) CANNOT BE RESUBMITTED UNTIL THE DRIVEWAY
 PERMIT APPLICATION (17060414) IS REVIEWED BY
 ENGINEERING.
  
  
  
  
  
  