| Date |
Text |
| 2017-06-23 09:19:35 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | AT SEPARATE GARAGE BUILDING |
| | |
| | E3601.6 SERVICE DISCONNECT REQUIRED. |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING |
| | OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE CONDUCTORS |
| | |
| | E3601.6.2 SERVICE DISCONNECT LOCATION. |
| | THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A |
| | READILY ACCESSIBLE |
| | LOCATION EITHER OUTSIDE OF A BUILDING OR INSIDE NEAREST |
| | THE POINT OF ENTRANCE |
| | OF THE SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS |
| | SHALL NOT BE INSTALLED |
| | IN BATHROOMS. |
| | |
| | E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) |
| | OR BRANCH CIRCUIT(S). |
| | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| | CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM |
| | INSTALLED IN ACCORDANCE WITH |
| | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) |
| | SHALL BE CONNECTED IN A |
| | MANNER SPECIFIED IN SECTION E3607.3.1 OR, FOR EXISTING |
| | PREMISES WIRING SYSTEMS |
| | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE |
| | GROUNDING ELECTRODE(S) REQUIRED IN SECTION E3608 SHALL |
| | BE INSTALLED |
| | |
| | 225.31 DISCONNECTING MEANS |
| | MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL |
| | UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE BUILDING OR STRUCTURE. |
| | |
| | 225.32 LOCATION |
| | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER |
| | INSIDE OR OUTSIDE |
| | OF THE BUILDING OR STRUCTURE SERVED OR WHERE THE |
| | CONDUCTORS |
| | PASS THROUGH THE BUILDING OR STRUCTURE. THE |
| | DISCONNECTING |
| | MEANS SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST |
| | THE POINT |
| | OF ENTRANCE OF THE CONDUCTORS |
| | |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED |
| | BY A FEEDER(S) OR BRANCH CIRCUIT(S) |
| | (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S) |
| | SUPPLIED |
| | BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE |
| | OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE |
| | WITH |
| | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE |
| | CONDUCTOR(S) SHALL |
| | BE CONNECTED IN ACCORDANCE WITH 250.32(B) OR (C). WHERE |
| | THERE |
| | IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING |
| | ELECTRODE(S) |
| | REQUIRED IN 250.50 SHALL BE INSTALLED. |
| | |
| | AT MAIN HOUSE |
| | |
| | OUTLET SPACING SHALL MEET THE FOLLOWING: |
| | |
| | E3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 |
| | FEET (1829 MM), |
| | FROM A RECEPTACLE OUTLET. |
| | |
| | E3901.11 FOYERS. |
| | FOYERS THAT ARE NOT PART OF A HALLWAY IN ACCORDANCE |
| | WITH SECTION E3901.10 |
| | AND THAT HAVE AN AREA THAT IS GREATER THAN 60 FT2 (5.57 |
| | M2) SHALL HAVE A |
| | RECEPTACLE(S) LOCATED IN EACH WALL SPACE THAT IS 3 FEET |
| | (914 MM) OR MORE |
| | IN WIDTH AND UNBROKEN BY DOORWAYS, FLOOR-TO-CEILING |
| | WINDOWS, AND SIMILAR |
| | OPENINGS. |
| | |
| | PANELS IN MAIN HOUSE WILL HAVE TO MEET THE SAME |
| | REQUIREMENTS AS THE GARGE PANEL. |
| | SEE ABOVE FOR DISCONNECTING MEANS AND GROUNDING. |
| | |
| | LOCATION OF PANEL A1 NOT SHOWN ON DRAWINGS |
| | |
| | ELEVATOR NOT SHOWN ON LOAD CALCULATION |
| | |
| | BOTH STRUCTURES |
| | |
| | 250.94 BONDING FOR OTHER SYSTEMS |
| | AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM |
| | BONDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE |
| | PROVIDED |
| | EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR |
| | METERING EQUIPMENT |
| | ENCLOSURE AND AT THE DISCONNECTING MEANS FOR ANY |
| | ADDITIONAL |
| | BUILDINGS OR STRUCTURES |
| | |
| | |