2017-06-23 09:19:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 AT SEPARATE GARAGE BUILDING
  
 E3601.6 SERVICE DISCONNECT REQUIRED.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING
 OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE CONDUCTORS
  
 E3601.6.2 SERVICE DISCONNECT LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE
 LOCATION EITHER OUTSIDE OF A BUILDING OR INSIDE NEAREST
 THE POINT OF ENTRANCE
 OF THE SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS
 SHALL NOT BE INSTALLED
 IN BATHROOMS.
  
 E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S).
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH
 SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S)
 SHALL BE CONNECTED IN A
 MANNER SPECIFIED IN SECTION E3607.3.1 OR, FOR EXISTING
 PREMISES WIRING SYSTEMS
 ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE
 GROUNDING ELECTRODE(S) REQUIRED IN SECTION E3608 SHALL
 BE INSTALLED
  
 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING OR STRUCTURE.
  
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE
 OF THE BUILDING OR STRUCTURE SERVED OR WHERE THE
 CONDUCTORS
 PASS THROUGH THE BUILDING OR STRUCTURE. THE
 DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST
 THE POINT
 OF ENTRANCE OF THE CONDUCTORS
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED
 BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE
 OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE
 WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL
 BE CONNECTED IN ACCORDANCE WITH 250.32(B) OR (C). WHERE
 THERE
 IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING
 ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
 AT MAIN HOUSE
  
 OUTLET SPACING SHALL MEET THE FOLLOWING:
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET (1829 MM),
 FROM A RECEPTACLE OUTLET.
  
 E3901.11 FOYERS.
 FOYERS THAT ARE NOT PART OF A HALLWAY IN ACCORDANCE
 WITH SECTION E3901.10
 AND THAT HAVE AN AREA THAT IS GREATER THAN 60 FT2 (5.57
 M2) SHALL HAVE A
 RECEPTACLE(S) LOCATED IN EACH WALL SPACE THAT IS 3 FEET
 (914 MM) OR MORE
 IN WIDTH AND UNBROKEN BY DOORWAYS, FLOOR-TO-CEILING
 WINDOWS, AND SIMILAR
 OPENINGS.
  
 PANELS IN MAIN HOUSE WILL HAVE TO MEET THE SAME
 REQUIREMENTS AS THE GARGE PANEL.
 SEE ABOVE FOR DISCONNECTING MEANS AND GROUNDING.
  
 LOCATION OF PANEL A1 NOT SHOWN ON DRAWINGS
  
 ELEVATOR NOT SHOWN ON LOAD CALCULATION
  
 BOTH STRUCTURES
  
 250.94 BONDING FOR OTHER SYSTEMS
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM
 BONDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE
 PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT
 ENCLOSURE AND AT THE DISCONNECTING MEANS FOR ANY
 ADDITIONAL
 BUILDINGS OR STRUCTURES
  
  