| 2017-06-22 18:06:37 | RESIDENTIAL (R3) CABANA, MECHANICAL REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- A/C PLANS DOESN'T MATCH PLAN SUBMITTED FOR THE | | | CABANA CONVERSION UNDER MASTER PERMIT 16090104. REVISE | | | AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 2- A/C PLANS TO HAVE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 3- A/C PLAN TO HAVE THE EQUIPMENT MANUFACTURER AND | | | MODEL NUMBER SPECIFIED ON EQUIPMENT SIZING CALCULATIONS | | | AS REQUIRED BY SEC. 107.3.5.3(10) CITY AMENDMENTS. | | | | | | 4- EQUIPMENT LISTED ON THE EQUIPMENT SIZING | | | CALCULATIONS DOESN'T MATCH EQUIPMENT SHOWN ON THE AHRI | | | CERTIFICATE PROVIDED. REVISE AS REQUIRED TO MATCH. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|