2017-06-22 18:06:37RESIDENTIAL (R3) CABANA, MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- A/C PLANS DOESN'T MATCH PLAN SUBMITTED FOR THE
 CABANA CONVERSION UNDER MASTER PERMIT 16090104. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- A/C PLANS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- A/C PLAN TO HAVE THE EQUIPMENT MANUFACTURER AND
 MODEL NUMBER SPECIFIED ON EQUIPMENT SIZING CALCULATIONS
 AS REQUIRED BY SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 4- EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS DOESN'T MATCH EQUIPMENT SHOWN ON THE AHRI
 CERTIFICATE PROVIDED. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
  