| 2017-06-16 18:04:08 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- INFORMATION MARKED ON SHEET 7 OF 13 OF FLORIDA |
| | PRODUCT APPROVAL FL13757-R5 SUBMITTED IS NOT CLEAR. IT |
| | IS MISSING INFORMATION. THE HAND WRITTEN INFORMATION |
| | BELOW #1,2,3 IS NOT LEGIBLE. IT'S NOT CLEAR IF OPENING |
| | #4 IS GOING TO HAVE A BUILTOUT INSTALLATION AT TOP OF |
| | CONNECTION. IF SO, THEN NEED TO PROVIDE LEGIBLE |
| | INFORMATION AND NEED TO REVIEW TABLE "C" ON SHEET 6 OF |
| | 13. THE SPAN OF THE SHUTTERS HAVE AN IMPACT ON THE |
| | DESIGN PRESSURES. THEREFORE, THE BUILDOUT INSTALLATION |
| | MAY NOT BE ALLOWED. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 2- INSTALLATION SCHEDULE SUBMITTED SPECIFIES THAT THE |
| | SUBSTRATE AT THE TOP AND BOTTOM OF SHUTTERS IS "SOLID |
| | CONCRETE". ACCORDING TO CITY RECORDS THE TOP SUBSTRATE |
| | IS SOLID CONCRETE BECAUSE THEY HAVE PRECAST LINTELS, |
| | BUT THERE ARE NO SPECIFICATIONS. FOR WINDOW SILLS WITH |
| | SOLID CONCRETE. REVISE INSTALLATION SCHEDULE USING THE |
| | TABLES FOR CONCRETE BLOCK OR PROVIDE PROOF THAT THE |
| | WINDOW SILLS HAVE THE SOLID CONCRETE WITH THE REQUIRED |
| | CONCRETE STRENGTH. SEC. 107.2.1 CITY AMENDMENTS. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |