Plan Review Notes
Plan Review Notes For Permit 17060359
Permit Number 17060359
Review Stop P
Sequence Number 4
Notes
Date Text
2018-03-17 14:25:504TH REVIEW: FBC 2014 5TH EDITION
  
 DENIED
  
 1. PAGE A-4 BATHROOM LEGEND LIST GRAB BARS MISSING
 DIMENSIONS ON THE SIDE WALL VIEW. TO COMPLY WITH
 FBC-ACC 604.5.1 SIDE WALL. ALSO, SHOW THE TOILET PAPER
 HOLDER TO COMPLY WITH 2014 FBC-ACC 604.7 AND BE 7"-9"
 FROM THE LIP TO THE CENTER OF THE ROLL OR CENTER OF THE
 FIRST ROLL.
 2. THE VOIDED SET OF THE PLAN, P1 HAD AN ISOMETRIC
 DRAWING, NOTES, AND INFORMATION THAT IS NEEDED FOR THE
 FIELD, P-2 WAS ADDED AND THIS INFORMATION SHOULD HAVE
 BEEN TRANSPIRED TO REFLECT WORK. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1
 3. NEW GREASE TRAP INTERCEPTOR APPLICATION AND
 INSPECTION ARE REQUIRED WPB AMENDMENTS TO THE FBC SEC.
 105.1 REQUIRED. WPB ORDINANCE SEC. 90-125. -
 APPLICATION, CONSTRUCTION, AND CONNECTION TO CWPBSS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  