2018-03-13 13:27:514TH REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC
 PERMIT #17060359
 3/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M1: THE RTU EQUIPMENT SCHEDULE AT THE BOTTOM OF THE
 PLAN SHEETS SHOWS 3 EXISTING 5-TON SYSTEMS, HOWEVER THE
 EQUIPMENT SCHEDULES AT THE THE CENTERTOP OF THE SHEET
 SHOW EXISTING 5-TON AND 3.5 TON SYSTEMS, AND ONE NEW
 5-TON SYSTEM- SECTION 107.2.1 WPB AMENDMENTS
  
 2) M1: THE AIR BALANCE CALCULATION SHOWS RTU-2
 PROVIDING 403 CFMS OF OUTDOOR AIR, HOWEVER THE PLAN
 SHOWS THE UNIT IS PROVIDING 230 CFMS- SECTION 107.2.1
  
 3) M1: PLEASE CLARIFY HOW THE NEW RTU-3, WHICH HAS NO
 DUCTWORK, AND IS LOCATED IN THE BACK OF THE HOUSE, IS
 SUPPLYING AIR TO THE DINING ROOM- SECTION 107.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  