| Plan Review Notes For Permit 17060359 |
| Permit Number |
17060359 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-03-13 13:27:51 | 4TH REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH | | | AMENDMENTS TO THE FBC | | | PERMIT #17060359 | | | 3/13/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M1: THE RTU EQUIPMENT SCHEDULE AT THE BOTTOM OF THE | | | PLAN SHEETS SHOWS 3 EXISTING 5-TON SYSTEMS, HOWEVER THE | | | EQUIPMENT SCHEDULES AT THE THE CENTERTOP OF THE SHEET | | | SHOW EXISTING 5-TON AND 3.5 TON SYSTEMS, AND ONE NEW | | | 5-TON SYSTEM- SECTION 107.2.1 WPB AMENDMENTS | | | | | | 2) M1: THE AIR BALANCE CALCULATION SHOWS RTU-2 | | | PROVIDING 403 CFMS OF OUTDOOR AIR, HOWEVER THE PLAN | | | SHOWS THE UNIT IS PROVIDING 230 CFMS- SECTION 107.2.1 | | | | | | 3) M1: PLEASE CLARIFY HOW THE NEW RTU-3, WHICH HAS NO | | | DUCTWORK, AND IS LOCATED IN THE BACK OF THE HOUSE, IS | | | SUPPLYING AIR TO THE DINING ROOM- SECTION 107.2.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|