| 2018-01-10 14:44:17 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES. |
| | PERMIT #17060359 |
| | 1/10/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: RECIRCULATION OF AIR FROM THE KITCHEN AC |
| | SYSTEM (RTU-1) INTO THE BAR AREA IS PROHIBITED PER |
| | TABLE 403.3 FOOTNOTE B. |
| | |
| | 2) M1: THE REQUESTED EXHAUST VENTILATION CALULATION AND |
| | EXHAUST SYSTEM FOR THE KITCHEN WERE NOT PROVIDED. |
| | |
| | 3) M1: THE PLAN SHOWS INADEQUATE AMOUNTS OF OUTDOOR AIR |
| | TO BE PROVIDED TO THE DINING ROOM AND BAR AREA. USING |
| | TABLE 403.3 I AM CALCULATING 1118 CFMS OF O/A REQUIRED |
| | FOR THE DINING ROOM AND BAR: 70 PERSONS PER 1000 SQ. |
| | FT.= 111 PERSONS FOR 1584 SQ. FT. X 7.5 CFMS PER SQ. |
| | FT= (833 CFMS) + 0.18 CFMS X 1584 SQ. FT.= (285 CFMS)- |
| | (TOTAL 1118 CFMS REQUIRED). |
| | |
| | 4) M1: DS DETECTORS SHALL BE LOCATED IN THE RETURN AIR |
| | SYSTEMS OF THE AIR HANDLERS- SECTION 606.2.1. THE PLAN |
| | SHOWS THE DETECTORS IN THE SUPPLY DUCTS. |
| | |
| | 5) M1: AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS ARE |
| | REQUIRED FOR THE O/A DUCTS SUPPLYING THE AC SYSTEMS- |
| | SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION. THE PLAN |
| | IS INCORRECTLY SPECIFYING MANUAL DAMPERS- PLEASE |
| | CORRECT. |
| | |
| | 6) M1: THE REQUESTED AIR BALANCE CALCULATIONS WERE NOT |
| | PROVIDED. |
| | |
| | 7) M2: PLEASE PROVIDE THE BTUH CAPACITIES OF ALL THE |
| | GAS-FIRED COOKING APPLIANCES IN THE EQUIPMENT SCHEDULE, |
| | AND CIRCLE, HIGHLIGHT THE MODEL NUMBERS AND BTUH |
| | CAPACITIES ON THE PRODUCT SUBMITTALS. PLEASE NOTE THAT |
| | THE SUBMITTED COMBUSTION AIR CALCULATIONS APPEAR TO BE |
| | BASED ON 166,000 BTU'S WHICH IS AN INCORRECT, VERY LOW |
| | AMOUNT WHEN COMPARED WITH THE CAPACITIES |
| | |
| | LISTED ON THE SUBMITTALS, AND SHOWN IN THE ISOMETRIC |
| | DRAWING- PLEASE CORRECT. |
| | |
| | 8) PROVIDE AC CALCULATIONS FOR THE NEW 5-TON RTU |
| | SYSTEM- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 9) M1, DETAIL M/6: REFER TO TABLE 1509.6.5 FBC-BUILDING |
| | AND PROVIDE THE CLEARANCE DISTANCE HEIGHT FROM THE |
| | FINISHED ROOF SURFACE TO THE BOTTOM SIDE OF THE RTU. |
| | PLEASE NOTE THAT THE RTU IS BEING IDENTIFIED AS |
| | A"CONDENSING " UNIT INSTEAD OF "PACKAGE" UNIT IN THE |
| | DETAIL. IT APPEARS THIS DETAIL DOES NOT ACTUALLY DEPICT |
| | WHAT TH3E ACTUAL INSTALLATION WILL BE BECAUSE NO |
| | DUCTWORK IS |
| | |
| | SHOWN CONNECTING TO THE UNIT. |
| | |
| | 10) M1, DETAIL M/6: THE ATTACHMENT DETAIL IS |
| | INCOMPLETE. MISSING DETAILS INCLUDE: A) NUMBER OF |
| | ANCHORING STRAPS AND HOW THEY ARE ATTACHED TO THE BEAM. |
| | B) ATTACHMENT OF THE CABLES TO THE BEAM. C) ENGINEERING |
| | FOR THE STAND, AND ATTACHMENT OF THE STAND TO THE |
| | STRUCTURE. D) WIND DESIGN CRITERIA: WIND SPEED, |
| | EXPOSUIRE CATEGORY, IMPORTANCE FACTOR, HEIGHT ABOVE |
| | GRADE, ETC. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |