| 2018-01-22 16:31:54 | PERMIT # 17060359 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | 3RD REVIEW |
| | |
| | 3RD REVIEW - SAME COMMENT |
| | 1) SHEET A4: THE DINING ROOM SEATING LAYOUT APPEARS |
| | OVER CONCENTRATED. THE "OCCUPANCY TAB" INDICATES THAT |
| | THE DINING & BAR AREA WAS CALCULATED AS 1584 SQ FT / |
| | 13. HOWEVER, PER NFPA 1, TABLE 14.8.1.2, THE |
| | CALCULATION SHOULD BE |
| | 1584 SQ FT / 15 FOR AN OCCUPANCY OF 105. THERE ARE |
| | ABOUT 14 SEATS OVER PERMITTED OCCUPANCY. |
| | PLEASE ALSO CONFIRM SEATING LAYOUT COMPLIES WITH NFPA |
| | 101: CHAPTER 12 - NEW ASSEMBLY OCCUPANCIES; |
| | SPECIFICALLY SECTIONS 12.2.5.7 AND 12.2.5.8, AISLE |
| | ACCESSWAYS AND AISLES SERVING SEATING AT TABLES. |
| | |
| | |
| | 2) 2ND REVIEW - SAME COMMENT: |
| | *** INCLUDE THE DIMENSIONS THAT SUPPORT YOUR COMPLIANCE |
| | OF THE CODE REQUIREMENT LISTED BELOW. THE DIMENSIONS |
| | FOR THE OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED IS NOT PROVIDED. NEITHER IS THE |
| | SEPARATION DISTANCE FOR THE TWO NEW ENTRY/EXIT |
| | DOORS.**** |
| | THE REMOTENESS BETWEEN THE REQUIRED EXITS SHALL COMPLY |
| | WITH THE FOLLOWING: |
| | 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 7.5.1.3.1 THROUGH 7.5.1.3.7. |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION |
| | THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES |
| | SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR |
| | OTHER EMERGENCY CONDITION. |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A |
| | DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE |
| | LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT |
| | LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT |
| | ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED |
| | IN 7.5.1.3.3 THROUGH 7.5.1.3.5. |
| | 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION |
| | DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2, |
| | SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED. |
| | |
| | 3) PLEASE CONFIRM THAT THIS SUITE IS PROTECTED WITH AN |
| | APPROVED FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM |
| | AND THAT A PERMIT WILL BE APPLIED FOR DUE TO ANY AND |
| | ALL CHANGES MADE TO THOSE SYSTEMS. SHEET A4 HAS |
| | CONFLICTING INFORMATION AS IT STATES THAT THERE WILL BE |
| | NO CHANGES, HOWEVER THERE ARE PORTIONS OF THE SUITE |
| | THAT HAVE WALLS BEING REMOVED OR ADDED, PER SHEETS A2 |
| | AND A3....THIS WILL AFFECT FIRE SPRINKLER AND FIRE |
| | ALARM COVERAGE. |
| | |
| | 4) NEW COMMENT: |
| | SHEETS A4 AND E2 DO NOT MATCH. ONE OF THE NEW |
| | ENTRY/EXIT DOORS AND EXIT SIGNS IS NOT SHOWN ON SHEET |
| | E2. PLEASE UPDATE SHEET E2. |
| | |
| | |
| | |
| | |