2018-01-22 16:31:54PERMIT # 17060359
 REVIEW COMMENTS - FIRE DEPARTMENT
 3RD REVIEW
  
 3RD REVIEW - SAME COMMENT
 1) SHEET A4: THE DINING ROOM SEATING LAYOUT APPEARS
 OVER CONCENTRATED. THE "OCCUPANCY TAB" INDICATES THAT
 THE DINING & BAR AREA WAS CALCULATED AS 1584 SQ FT /
 13. HOWEVER, PER NFPA 1, TABLE 14.8.1.2, THE
 CALCULATION SHOULD BE
 1584 SQ FT / 15 FOR AN OCCUPANCY OF 105. THERE ARE
 ABOUT 14 SEATS OVER PERMITTED OCCUPANCY.
 PLEASE ALSO CONFIRM SEATING LAYOUT COMPLIES WITH NFPA
 101: CHAPTER 12 - NEW ASSEMBLY OCCUPANCIES;
 SPECIFICALLY SECTIONS 12.2.5.7 AND 12.2.5.8, AISLE
 ACCESSWAYS AND AISLES SERVING SEATING AT TABLES.
  
  
 2) 2ND REVIEW - SAME COMMENT:
 *** INCLUDE THE DIMENSIONS THAT SUPPORT YOUR COMPLIANCE
 OF THE CODE REQUIREMENT LISTED BELOW. THE DIMENSIONS
 FOR THE OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED IS NOT PROVIDED. NEITHER IS THE
 SEPARATION DISTANCE FOR THE TWO NEW ENTRY/EXIT
 DOORS.****
 THE REMOTENESS BETWEEN THE REQUIRED EXITS SHALL COMPLY
 WITH THE FOLLOWING:
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED
 IN 7.5.1.3.3 THROUGH 7.5.1.3.5.
 7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7, THE MINIMUM SEPARATION
 DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2,
 SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED.
  
 3) PLEASE CONFIRM THAT THIS SUITE IS PROTECTED WITH AN
 APPROVED FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM
 AND THAT A PERMIT WILL BE APPLIED FOR DUE TO ANY AND
 ALL CHANGES MADE TO THOSE SYSTEMS. SHEET A4 HAS
 CONFLICTING INFORMATION AS IT STATES THAT THERE WILL BE
 NO CHANGES, HOWEVER THERE ARE PORTIONS OF THE SUITE
 THAT HAVE WALLS BEING REMOVED OR ADDED, PER SHEETS A2
 AND A3....THIS WILL AFFECT FIRE SPRINKLER AND FIRE
 ALARM COVERAGE.
  
 4) NEW COMMENT:
 SHEETS A4 AND E2 DO NOT MATCH. ONE OF THE NEW
 ENTRY/EXIT DOORS AND EXIT SIGNS IS NOT SHOWN ON SHEET
 E2. PLEASE UPDATE SHEET E2.
  
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  