| Plan Review Notes For Permit 17060359 |
| Permit Number |
17060359 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-01-12 17:27:33 | ***CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE EXISTING DOOR IS SHOWN AS PERMANENTLY LOCKED. | | | SEE FBC B 1008.1.9, | | | | | | 9. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | 11. FBC 107, THE DESIGNER OF RECORD IS TO REVIEW | | | PRODUCT APPROVALS AND DELEGATED ENGINEERING. A DOOR | | | DETAIL SIGNED AND SEALED BY THOMAS TWOMEY, PE WAS | | | INCLUDED AND DOES NOT INCLUDE PANIC DEVICES (STATES "NO | | | PANIC") AND INCLUDES A LOCK, SEE FBC B 1008. | | | | | | 3RD REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED. | | | SAME DETAIL PROVIDED, NO PRODUCT APPROVAL SUBMITTED. | | | | | | 12. FLORIDA STATUTE 553.80, A 4X PLAN REVIEW FEE WILL | | | BE ASSESSED IF COMMENTS NOT ADDRESSED A THIRD TIME. | | | | | | |
|