| 2017-09-07 13:06:47 | 9/7/17 2ND REVIEW PLUMBING DENIED |
| | |
| | 1.BASED ON THE OCCUPANCY LOAD OF 162 YOUR REQUIRED TO |
| | HAVE 2 TOILETS FOR EACH SEX TO COMPLY WITH FBC-PLB |
| | 403.1 A-2 RESTAURANTS. I WOULD ADVISED YOU TO ASK FOR |
| | RELIEF FROM THE CHIEF PLUMBING INSPECTOR OR LOWER YOUR |
| | OCCUPANCY |
| | |
| | 2.PAGE A-4 BATHROOM LEGEND LIST GRAB BARS TO BE |
| | INSTALLED @ 33". TO COMPLY WITH FBC-ACC 609.4 GRAB BARS |
| | SHALL BE 33"-36" TO THE TOP OF THE GRIPPING SURFACE. |
| | |
| | 3.PAGE A-4 BATHROOM LEGEND LIST THE TOILET PAPER |
| | DISPENSER TO BE INSTALLED @ 24" FROM THE HORIZONTAL |
| | LIP, THIS IS INCORRECT AND MUST COMPLY WITH FBC-ACC |
| | 604.7 AND BE 7"-9" FROM THE LIP TO THE CENTER OF THE |
| | ROLL OR CENTER OF THE FIRST ROLL. |
| | |
| | 4.PLAN SHOWS A DEEP FRYER BEING ADDED BUT IS NOT SHOWN |
| | ON THE ELECTRIC PLAN. IF DEEP FRYER IS GOING TO BE GAS |
| | UNIT A SEPARATE PERMIT AND DRAWINGS WILL BE REQUIRED. |
| | |
| | 5.WITH THE GAS WATER HEATER NOW BEING IN A CLOSET |
| | PLEASE PROVIDE SPECIFICATIONS FOR THE WATER HEATER AND |
| | THE REQUIRED MAKE UP AIR FOR THE ROOM TO COMPLY WITH |
| | FBC-FUEL GAS SECTION 304. FBC 102.7.1 |
| | |
| | 6.PROVIDE SPECIFICATIONS ON EXISTING GREASE TRAP AND |
| | SIZING BASED ON PLANNED OCCUPANCY LOAD |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |